| 2018-07-17 17:36:07 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18070030 |
| | 7/17/18 |
| | |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) IN ORDER TO PROVIDE A COMPLETE REVIEW, THE ARCHITECT |
| | OF RECORD SHALL PROVIDE A LIFE SAFETY PLAN WHICH SHALL |
| | INCLUDE THE OCCUPANCY CLASSIFCATION(S) OF THE FACILITY, |
| | OCCUPANT LOAD, FIRE SPRINKLER CLASSIFICATION, LOCATION |
| | OF FIRE SEPARATIONS AND HOURLY FIRE-RATINGS, |
| | FIRESTOPPING FOR PIPES, CONDUITS, AND DUCTWORK, EGRESS |
| | PATHS AND TRAVEL DISTANCES, ETC.- SECTION 107.2.1 WPB. |
| | |
| | 2) IN ORDER TO PROVIDE A COMPLETE REVIEW, THE ARCHITECT |
| | SHALL INDICATE THE CLASSIFCATION OF WORK AS OUTLINED IN |
| | CHAPTER 5 FBC EX. THIS APPEARS TO BE A CHANGE OF |
| | OCCUPANCY AS DEFINED IN SECTION 202 FBC EX. PLEASE SEE |
| | SECTION 506 AND CHAPTER 10 FOR ALL REQUIREMENTS. |
| | |
| | 3) M-100: SUBMIT MANUFACTURER'S SPECIFICATIONS AND/OR |
| | CUT SHEETS FOR ALL EQUIPMENT LISTED IN THE SCHEDULE |
| | INCLUDING THE CHILLER, BOILER, STILLS ETC. THE SPECS |
| | SHALL INDICATE THE LISTING AND LABELING, OR TESTING |
| | STANDARD APPLIED TO EACH PIECE OF EQUIPMENT- SECTION |
| | 107.2.1 WPB. |
| | |
| | 4) M-101: SHOW PIPING RUN FROM MAKEUP WATER UNIT TO THE |
| | CHILLER. |
| | |
| | 5) SHEET M-102: PLEASE INCLUDE VENTILATION CALCULATIONS |
| | FOR THE LAB, BOTTLING ROOM, AND RECEPTION/TASTING ROOM- |
| | SEE SECTION 809.2 FBC EX, AND TABLE 403.1.1 FBC M. |
| | PLEASE NOTE THAT THE LAB ROOM REQUIRES EXHAUST |
| | VENTILATION PER TABLE 403.1.1. |
| | |
| | 6) M-102: THE LOUVER SCHEDULE INDICATES "CART STORAGE |
| | AREA" WHICH APPEARS TO BE AN INCORRECT IDENTIFCATION OF |
| | THE DISTILLING AND PROCESSING AREA. PLEAE PROVIDE A |
| | FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE |
| | LOUVER. |
| | |
| | 7) M-103: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | GAS-FIRED STILLS, AND INDICATE HOW THE COMBUSTION AIR |
| | WILL BE PROVIDED- SECTION 304 FBC FG. |
| | |
| | 8) PROVIDE WIND LOAD ENGINEERING AND INSTALLATION |
| | DETAILS FOR THE CHILLER, BOILER, PUMPS, AND ALL OTHER |
| | ASSOCIATED EXTERIOR EQUIPMENT AND SUPPORTS SHOWN ON |
| | SHEET M-100- SECTION 301.15 FBC M. |
| | |
| | 9) M-003 & M-104: INCLUDE THE TRYMER PIPE INSULATION IN |
| | THE SPECIFICATIONS, AND ON WHICH PIPING SYSTEMS THE |
| | INSULATION IS TO BE INSTALLED- CHILLER OR BOILER |
| | PIPING, OR BOTH. INDICATE THE THICKNESS OF INSULATION |
| | TO BE INSTALLED AND CLARIFY IF THE INSULATION IS TESTED |
| | AND RATED FOR EXTERIOR USE, OR IF ANOTHER PRODUCT WILL |
| | BE USED FOR THE EXTERIOR PIPING- SEE SECTION C403.2.10 |
| | FBC EC. |
| | |
| | 10) PLEASE PROVIDE A PLAN THAT SHOWS THE REQUIRED |
| | WORKING CLEARANCES AROUND THE STILLS, KETTLES, AS |
| | REQUIRED BY THE LISTING AGENCY OR THE MANUFACTURER, AND |
| | CLARIFY IF THE EXISTING SLAB HAS BEEN EVALUATED FOR THE |
| | INCREASED LOADS OF THE DISTILLERY EQUIPMENT- SECTION |
| | 107.2.1 WPB. |
| | |
| | 11) CLARIFY IF THE EXISTING SLAB HAS BEEN EVALUATED FOR |
| | THE INCREASED LOADS OF THE DISTILLERY TANKS, KETTLES, |
| | STILLS ETC, AND PROVIDE ANCHORING DETAILS. |
| | |
| | 12) THE $320,000.00 PERMIT VALUE APPEARS TO BE LOW FOR |
| | THE SCOPE OF THE PROPOSED PROJECT. PLEASE PROVIDE |
| | CONTRACTS, INVOICES, ESTIMATES ETC. THAT SHOW THE TOTAL |
| | COST OF THE PROJECT INCLUDING, LABOR, MATERIALS, |
| | EQUIPMENT, APPLIANCES, FIXTURES, DESIGN FEES, SITE |
| | WORK, OVERHEAD AND PROFIT- SECTION 109.3 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |