 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) A LIFE SAFETY PLAN (SHEET A250) IS IDENTIFIED ON THE
 SHEET INDEX, HOWEVER IT WAS NOT PROVIDED WITH THIS
 SUBMISSION.
 PLEASE PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 2) THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.3
 OF NFPA 101 FLORIDA EDITION 2015. FOR NON-SEPARATED
 MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE
 SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO
 THE BUILDING.
  
 3) PLEASE PROVIDE DETAILS REGARDING THE HAZARD OF
 CONTENTS, AS DEFINED BY NFPA 101, CHAPTER 6.
 6.2 HAZARD OF CONTENTS.
 6.2.1 GENERAL.
 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF
 CONTENTS SHALL BE THE RELATIVE DANGER OF THE START AND
 SPREAD OF FIRE, THE DANGER OF SMOKE OR GASES GENERATED,
 AND THE DANGER OF EXPLOSION OR OTHER OCCURRENCE
 POTENTIALLY ENDANGERING THE LIVES AND SAFETY OF THE
 OCCUPANTS OF THE BUILDING OR STRUCTURE.
 6.2.1.2 HAZARD OF CONTENTS SHALL BE CLASSIFIED BY THE
 REGISTERED DESIGN PROFESSIONAL (RDP) OR OWNER AND
 SUBMITTED TO THE AUTHORITY HAVING JURISDICTION FOR
 REVIEW AND APPROVAL ON THE BASIS OF THE CHARACTER OF
 THE CONTENTS AND THE PROCESSES OR OPERATIONS CONDUCTED
 IN THE BUILDING OR STRUCTURE.
 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT
 DEGREES OF HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS
 OF A BUILDING OR STRUCTURE, THE MOST HAZARDOUS SHALL
 GOVERN THE CLASSIFICATION, UNLESS HAZARDOUS AREAS ARE
 SEPARATED OR PROTECTED AS SPECIFIED IN SECTION 8.7 AND
 THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH 43.
  
 6.2.2 CLASSIFICATION OF HAZARD OF CONTENTS.
 6.2.2.1* GENERAL. THE HAZARD OF CONTENTS OF ANY
 BUILDING OR STRUCTURE SHALL BE CLASSIFIED AS LOW,
 ORDINARY, OR HIGH IN ACCORDANCE WITH 6.2.2.2, 6.2.2.3,
 AND 6.2.2.4.
 6.2.2.2* LOW HAZARD CONTENTS. LOW HAZARD CONTENTS SHALL
 BE CLASSIFIED AS THOSE OF SUCH LOW COMBUSTIBILITY THAT
 NO SELFPROPAGATING FIRE THEREIN CAN OCCUR.
 6.2.2.3* ORDINARY HAZARD CONTENTS. ORDINARY HAZARD
 CONTENTS SHALL BE CLASSIFIED AS THOSE THAT ARE LIKELY
 TO BURN WITH MODERATE RAPIDITY OR TO GIVE OFF A
 CONSIDERABLE VOLUME OF SMOKE.
 6.2.2.4* HIGH HAZARD CONTENTS. HIGH HAZARD CONTENTS
 SHALL BE CLASSIFIED AS THOSE THAT ARE LIKELY TO BURN
 WITH EXTREME RAPIDITY OR FROM WHICH EXPLOSIONS ARE
 LIKELY. (FOR MEANS OF EGRESS REQUIREMENTS, SEE SECTION
 7. 11.)
  
 4) PLEASE PROVIDE THE MANUFACTURER'S
 SPECIFICATIONS/DATA SHEET FOR ALL DISTILLNG AND BREWING
 EQUIPMENT BEING USED.
  
 5) PLEASE PROVIDE AN OUTLINE DETAILING THE DISTILLING
 AND/OR BREWING PROCESS.
  
 6) PLEASE BE ADVISED: WHERE A FIRE SPRINKLER AND/OR
 FIRE ALARM SYSTEM IS REQUIRED PER THE FLORIDA FIRE
 CODE, ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. (SEE FLORIDA ADMINISTRATIVE CODE 61G15
 FOR FULL DETAIL REQUIREMENTS.)
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 7) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  