| 2018-07-08 12:46:07 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THE INTERIOR LIGHTING POWER ALLOWANCE SCHEDULE ON |
| | SHEET E101 SPECIFIES THE WRONG CODE FOR DESIGN. PROVIDE |
| | CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES ABOVE) |
| | 2. LIGHTING CONTROL IS NOT SHOWN IN DETAILS OR ON PLAN. |
| | PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2 |
| | 3. SHEET E102, SERVICE KEY NOTE 2 STATES THAT A NEW 600 |
| | AMP SERVICE IS PROPOSED, WHILE THE RISER DIAGRAM SHOWS |
| | AN 800 AMP SERVICE. PROVIDE CLARIFICATION AND/OR |
| | CORRECTION. WPB FBC 107.2.1 |
| | 4. PROVIDE COMPLETE RISER DIAGRAM, SHOWING ALL DETAILS |
| | OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. PLAN CURRENTLY |
| | ONLY SHOWS THE NEW PROPOSED SERVICE, NOT THE EXISTING |
| | THAT IS TO REMAIN. NEC 215.5, 230, 250.50, 250.94, |
| | 408.30; WPB FBC 107.2.1 |
| | 5. PER NEC 230.2, ONLY ONE SERVICE IS PERMITTED UNLESS |
| | PERMITTED IN 230.2(A) THROUGH (D). EOR HAS NOT DETAILED |
| | WHY THE ADDITIONAL SERVICE IS REQUESTED. PROVIDE |
| | DETAILS OF WHY THE EXISTING SERVICE IS NOT ADEQUATE. |
| | 6. MAINS MUST BE GROUPED PER NEC 230.72. PROVIDE |
| | CORRECTION. NEC 230.72 |
| | 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | PLAN CURRENTLY ONLY SHOWS CALCULATION FOR SERVICE |
| | DISCONNECT. NEC 110.9, 110.10 |
| | 8. PROVIDE AIC RATING OF EACH PANEL. NEC 110.3, 110.9; |
| | WPB FBC 107.2.1 |
| | 9. PROVIDE ACCURATE LOAD CALCULATION FOR EACH PANEL AND |
| | SERVICE. IT APPEARS THE LOAD FOR THE WATER HEATER IS |
| | MISSING. NEC 220 |
| | 10. PROVIDE PANEL SCHEDULE FOR EXISTING PANELS |
| | INDICATING ANY NEW OR ALTERED CIRCUITS, THE WIRE AND |
| | BREAKER SIZE FOR THESE CIRCUITS, AND GFCI PROTECTION OR |
| | LIGHTING CONTROL WHERE APPLICABLE TO COMPLY WITH CODE. |
| | NEC 210.8, 210.19, 210.20, 215.2, 215.5, 408.4; FBC EC |
| | C405 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |