Plan Review Notes
Plan Review Notes For Permit 18070030
Permit Number 18070030
Review Stop E
Sequence Number 1
Notes
Date Text
2018-07-08 12:46:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE INTERIOR LIGHTING POWER ALLOWANCE SCHEDULE ON
 SHEET E101 SPECIFIES THE WRONG CODE FOR DESIGN. PROVIDE
 CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES ABOVE)
 2. LIGHTING CONTROL IS NOT SHOWN IN DETAILS OR ON PLAN.
 PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
 3. SHEET E102, SERVICE KEY NOTE 2 STATES THAT A NEW 600
 AMP SERVICE IS PROPOSED, WHILE THE RISER DIAGRAM SHOWS
 AN 800 AMP SERVICE. PROVIDE CLARIFICATION AND/OR
 CORRECTION. WPB FBC 107.2.1
 4. PROVIDE COMPLETE RISER DIAGRAM, SHOWING ALL DETAILS
 OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. PLAN CURRENTLY
 ONLY SHOWS THE NEW PROPOSED SERVICE, NOT THE EXISTING
 THAT IS TO REMAIN. NEC 215.5, 230, 250.50, 250.94,
 408.30; WPB FBC 107.2.1
 5. PER NEC 230.2, ONLY ONE SERVICE IS PERMITTED UNLESS
 PERMITTED IN 230.2(A) THROUGH (D). EOR HAS NOT DETAILED
 WHY THE ADDITIONAL SERVICE IS REQUESTED. PROVIDE
 DETAILS OF WHY THE EXISTING SERVICE IS NOT ADEQUATE.
 6. MAINS MUST BE GROUPED PER NEC 230.72. PROVIDE
 CORRECTION. NEC 230.72
 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 PLAN CURRENTLY ONLY SHOWS CALCULATION FOR SERVICE
 DISCONNECT. NEC 110.9, 110.10
 8. PROVIDE AIC RATING OF EACH PANEL. NEC 110.3, 110.9;
 WPB FBC 107.2.1
 9. PROVIDE ACCURATE LOAD CALCULATION FOR EACH PANEL AND
 SERVICE. IT APPEARS THE LOAD FOR THE WATER HEATER IS
 MISSING. NEC 220
 10. PROVIDE PANEL SCHEDULE FOR EXISTING PANELS
 INDICATING ANY NEW OR ALTERED CIRCUITS, THE WIRE AND
 BREAKER SIZE FOR THESE CIRCUITS, AND GFCI PROTECTION OR
 LIGHTING CONTROL WHERE APPLICABLE TO COMPLY WITH CODE.
 NEC 210.8, 210.19, 210.20, 215.2, 215.5, 408.4; FBC EC
 C405
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  