| 2018-08-01 19:02:33 | 1ST REVIEW FBC-2017 BUILDING |
| | PERMIT #18070030 |
| | 415 SOUTHERN BLVD. |
| | TYPE OF CONSTRUCTION: ? |
| | OCCUPANCY TYPE: ? |
| | SPRINKLERED BLDG: NO |
| | LEVEL OF ALTERATION: LEVEL III ALTERATION, CHANGE OF |
| | OCCUPANCY |
| | |
| | CODES IN EFFECT: |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S. |
| | THIS IS TO ADVISE YOU OF THE OWNERS OR OPERATORS? |
| | RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL |
| | ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S. |
| | AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE- |
| | ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION |
| | TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO: |
| | * DEMOLITION OF ALL REGULATED STRUCTURES; |
| | * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES |
| | WHERE ASBESTOS IS DISTURBED OR REMOVED. |
| | NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY. |
| | |
| | FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT |
| | THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING |
| | HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT |
| | (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR |
| | POLLUTION CONTROL SECTION) |
| | |
| | 901 EVERNIA STREET |
| | WEST PALM BEACH, FL 33401 |
| | (561) 355-3070 |
| | |
| | 2) A LIFE SAFETY PLAN (SHEET A250) IS IDENTIFIED ON THE |
| | SHEET INDEX, HOWEVER IT WAS NOT PROVIDED WITH THIS |
| | SUBMISSION. PLEASE PROVIDE A LIFE SAFETY PLAN SHOWING |
| | TYPE OF CONSTRUCTION AND ALL OCCUPANCY TYPES, OCCUPANT |
| | LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY |
| | LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL, FIRE |
| | SPRINKLER CLASSIFICATION, LOCATION OF FIRE SEPARATIONS |
| | AND HOURLY FIRE-RATINGS, FIRESTOPPING FOR PIPES, |
| | CONDUITS, AND DUCTWORK, EGRESS PATHS AND TRAVEL |
| | DISTANCES, ETC.- SECTION 107.2.1 WPB AMENDMENTS |
| | |
| | 3) IN ORDER TO PROVIDE A COMPLETE REVIEW, THE ARCHITECT |
| | SHALL INDICATE THE CLASSIFICATION OF WORK AS OUTLINED |
| | IN CHAPTER 5 FBC EXISTING BUILDING. THIS APPEARS TO BE |
| | A CHANGE OF OCCUPANCY AS DEFINED IN SECTION 202 FBC EX. |
| | PLEASE SEE SECTION 506 AND CHAPTER 10 FOR ALL |
| | REQUIREMENTS. |
| | |
| | 4) THE BUILDING IS FUNCTIONING AS A MULTI-USE |
| | OCCUPANCY. INDICATE IF THE BUILDING IS DESIGNED FOR |
| | MIXED USE (NON-SEPARATED) OR SEPARATED USE PER SECTION |
| | 6.1.14.3 OF NFPA 101 FLORIDA EDITION 2015. FOR |
| | NON-SEPARATED MIXED USE OCCUPANCIES, THE MOST STRINGENT |
| | FIRE AND LIFE SAFETY REQUIREMENTS OF EACH OCCUPANCY |
| | SHALL APPLY TO THE BUILDING. |
| | |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS AND/OR CUT |
| | SHEETS FOR ALL EQUIPMENT LISTED IN THE SCHEDULE |
| | INCLUDING THE CHILLER, BOILER, STILLS ETC. THE SPECS |
| | SHALL INDICATE THE LISTING AND LABELING, OR TESTING |
| | STANDARD APPLIED TO EACH PIECE OF EQUIPMENT- SECTION |
| | 107.2.1 WPB. |
| | |
| | 6) PLEASE PROVIDE AN OUTLINE DETAILING THE DISTILLING |
| | AND/OR BREWING PROCESS THAT WILL OCCUR AT THIS |
| | FACILITY. FBC 107.2.1 |
| | |
| | 7) PLEASE PROVIDE DETAILS REGARDING THE MANUFACTURE, |
| | PROCESSING, GENERATION AND STORAGE OF HAZARDOUS |
| | MATERIALS AT THIS SITE PER NFPA 101, CHAPTER 6 AND FBC |
| | SECTION 307. |
| | [F]307.1 HIGH-HAZARD GROUP H. |
| | HIGH-HAZARD GROUP H OCCUPANCY INCLUDES, AMONG OTHERS, |
| | THE USE OF A BUILDING OR STRUCTURE, OR A PORTION |
| | THEREOF, THAT INVOLVES THE MANUFACTURING, PROCESSING, |
| | GENERATION OR STORAGE OF MATERIALS THAT CONSTITUTE A |
| | PHYSICAL OR HEALTH HAZARD IN QUANTITIES IN EXCESS OF |
| | THOSE ALLOWED IN CONTROL AREAS COMPLYING WITH SECTION |
| | 414, BASED ON THE MAXIMUM ALLOWABLE QUANTITY LIMITS FOR |
| | CONTROL AREAS SET FORTH IN TABLES 307.1(1) AND |
| | 307.1(2). HAZARDOUS OCCUPANCIES ARE CLASSIFIED IN |
| | GROUPS H-1, H-2, H-3, H-4 AND H-5 AND SHALL BE IN |
| | ACCORDANCE WITH THIS SECTION, THE REQUIREMENTS OF |
| | SECTION 415 AND THE FLORIDA FIRE PREVENTION CODE. |
| | HAZARDOUS MATERIALS STORED, OR USED ON TOP OF ROOFS OR |
| | CANOPIES, SHALL BE CLASSIFIED AS OUTDOOR STORAGE OR USE |
| | AND SHALL COMPLY WITH THE FLORIDA FIRE PREVENTION CODE. |
| | SEE FBC B TABLE 307.1(1) |
| | [F]307.1.2 HAZARDOUS MATERIALS. |
| | HAZARDOUS MATERIALS IN ANY QUANTITY SHALL CONFORM TO |
| | THE REQUIREMENTS OF THIS CODE, INCLUDING SECTION 414, |
| | AND THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | 8) SUBMIT TWO COPIES OF THE MATERIAL SAFETY DATA SHEETS |
| | (MSDS) FOR THE HAZARDOUS MATERIALS (FLAMMABLE LIQUIDS, |
| | ETC.) THAT WILL BE PRESENT AT THIS FACILITY. FBC B |
| | 307.1.2 |
| | |
| | 9) PROVIDE WIND LOAD ENGINEERING AND INSTALLATION |
| | DETAILS FOR THE CHILLER, BOILER, PUMPS, AND ALL OTHER |
| | ASSOCIATED EXTERIOR EQUIPMENT AND SUPPORTS. 2017 FBC-B |
| | 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 2. RISK CATEGORY. |
| | |
| | 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | |
| | 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 10) COMPONENTS & CLADDING |
| | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 11) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC. |
| | |
| | 12)W.P.B. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 13) CLARIFY IF THE EXISTING SLAB HAS BEEN EVALUATED FOR |
| | THE INCREASED LOADS OF THE DISTILLERY TANKS, KETTLES, |
| | STILLS ETC, AND PROVIDE ANCHORING DETAILS. FBC-B 1606 |
| | AND 1607 |
| | |
| | 14) PLEASE PROVIDE A PLAN THAT SHOWS THE REQUIRED |
| | WORKING CLEARANCES AROUND THE STILLS, KETTLES, AS |
| | REQUIRED BY THE LISTING AGENCY OR THE MANUFACTURER, AND |
| | CLARIFY IF THE EXISTING SLAB HAS BEEN EVALUATED FOR THE |
| | INCREASED LOADS OF THE DISTILLERY EQUIPMENT- SECTION |
| | 107.2.1 WPB. |
| | |
| | 15) 2017 FBC- ACCESSIBILITY - ADA |
| | 201.1 SCOPE. |
| | THIS CODE ESTABLISHES STANDARDS FOR ACCESSIBILITY TO |
| | PLACES OF PUBLIC ACCOMMODATION AND COMMERCIAL |
| | FACILITIES BY INDIVIDUALS WITH DISABILITIES. THIS CODE |
| | SHALL ALSO APPLY: TO STATE AND LOCAL GOVERNMENT |
| | FACILITIES PURSUANT TO SECTION 553.503, F.S.; TO |
| | PRIVATE CLUBS PURSUANT TO SECTION 553.505, F.S.; AND TO |
| | RESIDENTIAL BUILDINGS PURSUANT TO SECTION 553.504(2), |
| | F.S., AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN. ALL |
| | NEW OR ALTERED PUBLIC BUILDINGS AND FACILITIES, PRIVATE |
| | BUILDINGS AND FACILITIES, PLACES OF PUBLIC |
| | ACCOMMODATION AND COMMERCIAL FACILITIES SUBJECT TO THIS |
| | CODE SHALL COMPLY WITH THIS CODE. |
| | THIS CODE APPLIES TO: ALL AREAS OF NEWLY DESIGNED AND |
| | NEWLY CONSTRUCTED BUILDINGS AND FACILITIES AS |
| | DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN; |
| | PORTIONS OF ALTERED BUILDINGS AND FACILITIES AS |
| | DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN; |
| | A BUILDING OR FACILITY THAT IS BEING CONVERTED FROM |
| | RESIDENTIAL TO NONRESIDENTIAL OR MIXED USE AS DEFINED |
| | BY THE FLORIDA BUILDING CODE WHERE SUCH BUILDING OR |
| | FACILITY MUST, AT A MINIMUM, COMPLY WITH S. 553.508, |
| | F.S., AND THE REQUIREMENTS FOR ALTERATIONS AS |
| | DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN; |
| | BUILDINGS AND FACILITIES WHERE THE ORIGINAL |
| | CONSTRUCTION OR ANY FORMER ALTERATION OR RENOVATION WAS |
| | CARRIED OUT IN VIOLATION OF APPLICABLE PERMITTING LAW. |
| | |
| | 15-1) THE PLANS SHOW A RECEPTION/TASTING AREA THAT |
| | APPARENTLY WILL BE OPEN TO THE PUBLIC. SPECIFY WHICH |
| | AREAS WILL BE OPEN TO THE PUBLIC FOR TOURS, ETC. FBC |
| | 107.2.1 |
| | |
| | 15-2) 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS |
| | 553.501-553.513, F.S., AND THE ADA STANDARDS FOR |
| | ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY |
| | BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE |
| | SECTIONS FROM THE DUTY TO PROVIDE VERTICAL |
| | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE |
| | OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE |
| | STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH |
| | BUILDING, STRUCTURE OR FACILITY, EXCEPT FOR: |
| | (1)ELEVATOR PITS, ELEVATOR PENTHOUSES, MECHANICAL |
| | ROOMS, PIPING OR EQUIPMENT CATWALKS AND AUTOMOBILE |
| | LUBRICATION AND MAINTENANCE PITS AND PLATFORMS. |
| | (2)UNOCCUPIABLE SPACES, SUCH AS ROOMS, ENCLOSED SPACES |
| | AND STORAGE SPACES THAT ARE NOT DESIGNED FOR HUMAN |
| | OCCUPANCY, FOR PUBLIC ACCOMMODATIONS OR FOR WORK AREAS. |
| | (3)OCCUPIABLE SPACES AND ROOMS THAT ARE NOT OPEN TO THE |
| | PUBLIC AND THAT HOUSE NO MORE THAN FIVE PERSONS, |
| | INCLUDING, BUT NOT LIMITED TO EQUIPMENT CONTROL ROOMS |
| | AND PROJECTION BOOTHS. |
| | (4)THEATERS, CONCERT HALLS, AND STADIUMS, OR OTHER |
| | LARGE ASSEMBLY AREAS THAT HAVE STADIUM-STYLE SEATING OR |
| | TIERED SEATING IF SECTIONS 221 AND 802 ARE MET. |
| | (5)ALL PLAY AND RECREATION AREAS IF THE REQUIREMENTS OF |
| | CHAPTER 10 ARE MET. |
| | (6)ALL EMPLOYEE AREAS AS EXEMPTED BY 203.9. |
| | (7)FACILITIES, SITES AND SPACES EXEMPTED BY SECTION |
| | 203. |
| | BUILDINGS, STRUCTURES AND FACILITIES MUST, AT A |
| | MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE ADA |
| | STANDARDS FOR ACCESSIBLE DESIGN. |
| | ADVISORY 201.1 SCOPE. THESE REQUIREMENTS ARE TO BE |
| | APPLIED TO ALL AREAS OF A FACILITY UNLESS EXEMPTED, OR |
| | WHERE SCOPING LIMITS THE NUMBER OF MULTIPLE ELEMENTS |
| | REQUIRED TO BE ACCESSIBLE. FOR EXAMPLE, NOT ALL MEDICAL |
| | CARE PATIENT ROOMS ARE REQUIRED TO BE ACCESSIBLE; THOSE |
| | THAT ARE NOT REQUIRED TO BE ACCESSIBLE ARE NOT REQUIRED |
| | TO COMPLY WITH THESE REQUIREMENTS. HOWEVER, COMMON USE |
| | AND PUBLIC USE SPACES SUCH AS RECOVERY ROOMS, |
| | EXAMINATION ROOMS, AND CAFETERIAS ARE NOT EXEMPT FROM |
| | THESE REQUIREMENTS AND MUST BE ACCESSIBLE. |
| | FLORIDA VERTICAL ACCESSIBILITY REQUIRES ALL LEVELS IN |
| | ALL NEW BUILDINGS, STRUCTURES AND FACILITIES AND ALL |
| | ALTERED AREAS OF EXISTING BUILDINGS, STRUCTURES AND |
| | FACILITIES TO BE ACCESSIBLE TO PERSONS WITH |
| | DISABILITIES. ALL NEW AND ALTERED AREAS MUST COMPLY |
| | WITH THE ADA STANDARDS FOR ACCESSIBLE DESIGN INCLUDING |
| | REQUIREMENTS FOR ACCESSIBLE ROUTES. WHERE THE ADA |
| | STANDARDS DO NOT REQUIRE AN ACCESSIBLE ROUTE TO EACH |
| | AND EVERY LEVEL, THE FLORIDA REQUIREMENT MAY BE WAIVED |
| | DOWN TO THE REQUIREMENT OF THE ADA STANDARDS. |
| | |
| | 15-3) PROVIDE AN ACCESSIBLE ROUTE TO AND THROUGH THE |
| | PUBLIC AREAS. FBC-A 206.1 GENERAL. ACCESSIBLE ROUTES |
| | SHALL BE PROVIDED IN ACCORDANCE WITH 206 AND SHALL |
| | COMPLY WITH CHAPTER 4. |
| | |
| | 15-4) PROVIDE AN ACCESSIBLE BATHROOM. |
| | FBC-A 213 TOILET FACILITIES AND BATHING FACILITIES |
| | 213.1 GENERAL. |
| | WHERE TOILET FACILITIES AND BATHING FACILITIES ARE |
| | PROVIDED, THEY SHALL COMPLY WITH 213. WHERE TOILET |
| | FACILITIES AND BATHING FACILITIES ARE PROVIDED IN |
| | FACILITIES PERMITTED BY 206.2.3 EXCEPTIONS 1 AND 2 NOT |
| | TO CONNECT STORIES BY AN ACCESSIBLE ROUTE, TOILET |
| | FACILITIES AND BATHING FACILITIES SHALL BE PROVIDED ON |
| | A STORY CONNECTED BY AN ACCESSIBLE ROUTE TO AN |
| | ACCESSIBLE ENTRANCE. |
| | 213.2 TOILET ROOMS AND BATHING ROOMS. |
| | WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL |
| | COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH |
| | BATHING ROOM SHALL COMPLY WITH 603. |
| | |
| | 16) THE $320,000.00 PERMIT VALUE APPEARS TO BE LOW FOR |
| | THE SCOPE OF THE PROPOSED PROJECT. PLEASE PROVIDE |
| | CONTRACTS, INVOICES, ESTIMATES ETC. THAT SHOW THE TOTAL |
| | COST OF THE PROJECT INCLUDING, LABOR, MATERIALS, |
| | EQUIPMENT, APPLIANCES, FIXTURES, DESIGN FEES, SITE |
| | WORK, OVERHEAD AND PROFIT- SECTION 109.3 WPB. |
| | 109.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME OR MASTER PERMIT. |
| | |
| | 17) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION |
| | SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS |
| | MAY BE GENERATED DURING PLAN RESUBMISSION. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |