Plan Review Notes For Permit 18070030
Permit Number 18070030
Review Stop B
Sequence Number 1
Notes
Date Text
2018-08-01 19:02:331ST REVIEW FBC-2017 BUILDING
 PERMIT #18070030
 415 SOUTHERN BLVD.
 TYPE OF CONSTRUCTION: ?
 OCCUPANCY TYPE: ?
 SPRINKLERED BLDG: NO
 LEVEL OF ALTERATION: LEVEL III ALTERATION, CHANGE OF
 OCCUPANCY
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S.
 THIS IS TO ADVISE YOU OF THE OWNERS OR OPERATORS?
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  
 2) A LIFE SAFETY PLAN (SHEET A250) IS IDENTIFIED ON THE
 SHEET INDEX, HOWEVER IT WAS NOT PROVIDED WITH THIS
 SUBMISSION. PLEASE PROVIDE A LIFE SAFETY PLAN SHOWING
 TYPE OF CONSTRUCTION AND ALL OCCUPANCY TYPES, OCCUPANT
 LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY
 LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL, FIRE
 SPRINKLER CLASSIFICATION, LOCATION OF FIRE SEPARATIONS
 AND HOURLY FIRE-RATINGS, FIRESTOPPING FOR PIPES,
 CONDUITS, AND DUCTWORK, EGRESS PATHS AND TRAVEL
 DISTANCES, ETC.- SECTION 107.2.1 WPB AMENDMENTS
  
 3) IN ORDER TO PROVIDE A COMPLETE REVIEW, THE ARCHITECT
 SHALL INDICATE THE CLASSIFICATION OF WORK AS OUTLINED
 IN CHAPTER 5 FBC EXISTING BUILDING. THIS APPEARS TO BE
 A CHANGE OF OCCUPANCY AS DEFINED IN SECTION 202 FBC EX.
 PLEASE SEE SECTION 506 AND CHAPTER 10 FOR ALL
 REQUIREMENTS.
  
 4) THE BUILDING IS FUNCTIONING AS A MULTI-USE
 OCCUPANCY. INDICATE IF THE BUILDING IS DESIGNED FOR
 MIXED USE (NON-SEPARATED) OR SEPARATED USE PER SECTION
 6.1.14.3 OF NFPA 101 FLORIDA EDITION 2015. FOR
 NON-SEPARATED MIXED USE OCCUPANCIES, THE MOST STRINGENT
 FIRE AND LIFE SAFETY REQUIREMENTS OF EACH OCCUPANCY
 SHALL APPLY TO THE BUILDING.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS AND/OR CUT
 SHEETS FOR ALL EQUIPMENT LISTED IN THE SCHEDULE
 INCLUDING THE CHILLER, BOILER, STILLS ETC. THE SPECS
 SHALL INDICATE THE LISTING AND LABELING, OR TESTING
 STANDARD APPLIED TO EACH PIECE OF EQUIPMENT- SECTION
 107.2.1 WPB.
  
 6) PLEASE PROVIDE AN OUTLINE DETAILING THE DISTILLING
 AND/OR BREWING PROCESS THAT WILL OCCUR AT THIS
 FACILITY. FBC 107.2.1
  
 7) PLEASE PROVIDE DETAILS REGARDING THE MANUFACTURE,
 PROCESSING, GENERATION AND STORAGE OF HAZARDOUS
 MATERIALS AT THIS SITE PER NFPA 101, CHAPTER 6 AND FBC
 SECTION 307.
 [F]307.1 HIGH-HAZARD GROUP H.
 HIGH-HAZARD GROUP H OCCUPANCY INCLUDES, AMONG OTHERS,
 THE USE OF A BUILDING OR STRUCTURE, OR A PORTION
 THEREOF, THAT INVOLVES THE MANUFACTURING, PROCESSING,
 GENERATION OR STORAGE OF MATERIALS THAT CONSTITUTE A
 PHYSICAL OR HEALTH HAZARD IN QUANTITIES IN EXCESS OF
 THOSE ALLOWED IN CONTROL AREAS COMPLYING WITH SECTION
 414, BASED ON THE MAXIMUM ALLOWABLE QUANTITY LIMITS FOR
 CONTROL AREAS SET FORTH IN TABLES 307.1(1) AND
 307.1(2). HAZARDOUS OCCUPANCIES ARE CLASSIFIED IN
 GROUPS H-1, H-2, H-3, H-4 AND H-5 AND SHALL BE IN
 ACCORDANCE WITH THIS SECTION, THE REQUIREMENTS OF
 SECTION 415 AND THE FLORIDA FIRE PREVENTION CODE.
 HAZARDOUS MATERIALS STORED, OR USED ON TOP OF ROOFS OR
 CANOPIES, SHALL BE CLASSIFIED AS OUTDOOR STORAGE OR USE
 AND SHALL COMPLY WITH THE FLORIDA FIRE PREVENTION CODE.
 SEE FBC B TABLE 307.1(1)
 [F]307.1.2 HAZARDOUS MATERIALS.
 HAZARDOUS MATERIALS IN ANY QUANTITY SHALL CONFORM TO
 THE REQUIREMENTS OF THIS CODE, INCLUDING SECTION 414,
 AND THE FLORIDA FIRE PREVENTION CODE.
  
 8) SUBMIT TWO COPIES OF THE MATERIAL SAFETY DATA SHEETS
 (MSDS) FOR THE HAZARDOUS MATERIALS (FLAMMABLE LIQUIDS,
 ETC.) THAT WILL BE PRESENT AT THIS FACILITY. FBC B
 307.1.2
  
 9) PROVIDE WIND LOAD ENGINEERING AND INSTALLATION
 DETAILS FOR THE CHILLER, BOILER, PUMPS, AND ALL OTHER
 ASSOCIATED EXTERIOR EQUIPMENT AND SUPPORTS. 2017 FBC-B
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2. RISK CATEGORY.
  
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 10) COMPONENTS & CLADDING
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 11) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.
  
 12)W.P.B. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 13) CLARIFY IF THE EXISTING SLAB HAS BEEN EVALUATED FOR
 THE INCREASED LOADS OF THE DISTILLERY TANKS, KETTLES,
 STILLS ETC, AND PROVIDE ANCHORING DETAILS. FBC-B 1606
 AND 1607
  
 14) PLEASE PROVIDE A PLAN THAT SHOWS THE REQUIRED
 WORKING CLEARANCES AROUND THE STILLS, KETTLES, AS
 REQUIRED BY THE LISTING AGENCY OR THE MANUFACTURER, AND
 CLARIFY IF THE EXISTING SLAB HAS BEEN EVALUATED FOR THE
 INCREASED LOADS OF THE DISTILLERY EQUIPMENT- SECTION
 107.2.1 WPB.
  
 15) 2017 FBC- ACCESSIBILITY - ADA
 201.1 SCOPE.
 THIS CODE ESTABLISHES STANDARDS FOR ACCESSIBILITY TO
 PLACES OF PUBLIC ACCOMMODATION AND COMMERCIAL
 FACILITIES BY INDIVIDUALS WITH DISABILITIES. THIS CODE
 SHALL ALSO APPLY: TO STATE AND LOCAL GOVERNMENT
 FACILITIES PURSUANT TO SECTION 553.503, F.S.; TO
 PRIVATE CLUBS PURSUANT TO SECTION 553.505, F.S.; AND TO
 RESIDENTIAL BUILDINGS PURSUANT TO SECTION 553.504(2),
 F.S., AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN. ALL
 NEW OR ALTERED PUBLIC BUILDINGS AND FACILITIES, PRIVATE
 BUILDINGS AND FACILITIES, PLACES OF PUBLIC
 ACCOMMODATION AND COMMERCIAL FACILITIES SUBJECT TO THIS
 CODE SHALL COMPLY WITH THIS CODE.
 THIS CODE APPLIES TO: ALL AREAS OF NEWLY DESIGNED AND
 NEWLY CONSTRUCTED BUILDINGS AND FACILITIES AS
 DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN;
 PORTIONS OF ALTERED BUILDINGS AND FACILITIES AS
 DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN;
 A BUILDING OR FACILITY THAT IS BEING CONVERTED FROM
 RESIDENTIAL TO NONRESIDENTIAL OR MIXED USE AS DEFINED
 BY THE FLORIDA BUILDING CODE WHERE SUCH BUILDING OR
 FACILITY MUST, AT A MINIMUM, COMPLY WITH S. 553.508,
 F.S., AND THE REQUIREMENTS FOR ALTERATIONS AS
 DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN;
 BUILDINGS AND FACILITIES WHERE THE ORIGINAL
 CONSTRUCTION OR ANY FORMER ALTERATION OR RENOVATION WAS
 CARRIED OUT IN VIOLATION OF APPLICABLE PERMITTING LAW.
  
 15-1) THE PLANS SHOW A RECEPTION/TASTING AREA THAT
 APPARENTLY WILL BE OPEN TO THE PUBLIC. SPECIFY WHICH
 AREAS WILL BE OPEN TO THE PUBLIC FOR TOURS, ETC. FBC
 107.2.1
  
 15-2) 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS
 553.501-553.513, F.S., AND THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY, EXCEPT FOR:
 (1)ELEVATOR PITS, ELEVATOR PENTHOUSES, MECHANICAL
 ROOMS, PIPING OR EQUIPMENT CATWALKS AND AUTOMOBILE
 LUBRICATION AND MAINTENANCE PITS AND PLATFORMS.
 (2)UNOCCUPIABLE SPACES, SUCH AS ROOMS, ENCLOSED SPACES
 AND STORAGE SPACES THAT ARE NOT DESIGNED FOR HUMAN
 OCCUPANCY, FOR PUBLIC ACCOMMODATIONS OR FOR WORK AREAS.
 (3)OCCUPIABLE SPACES AND ROOMS THAT ARE NOT OPEN TO THE
 PUBLIC AND THAT HOUSE NO MORE THAN FIVE PERSONS,
 INCLUDING, BUT NOT LIMITED TO EQUIPMENT CONTROL ROOMS
 AND PROJECTION BOOTHS.
 (4)THEATERS, CONCERT HALLS, AND STADIUMS, OR OTHER
 LARGE ASSEMBLY AREAS THAT HAVE STADIUM-STYLE SEATING OR
 TIERED SEATING IF SECTIONS 221 AND 802 ARE MET.
 (5)ALL PLAY AND RECREATION AREAS IF THE REQUIREMENTS OF
 CHAPTER 10 ARE MET.
 (6)ALL EMPLOYEE AREAS AS EXEMPTED BY 203.9.
 (7)FACILITIES, SITES AND SPACES EXEMPTED BY SECTION
 203.
 BUILDINGS, STRUCTURES AND FACILITIES MUST, AT A
 MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE ADA
 STANDARDS FOR ACCESSIBLE DESIGN.
 ADVISORY 201.1 SCOPE. THESE REQUIREMENTS ARE TO BE
 APPLIED TO ALL AREAS OF A FACILITY UNLESS EXEMPTED, OR
 WHERE SCOPING LIMITS THE NUMBER OF MULTIPLE ELEMENTS
 REQUIRED TO BE ACCESSIBLE. FOR EXAMPLE, NOT ALL MEDICAL
 CARE PATIENT ROOMS ARE REQUIRED TO BE ACCESSIBLE; THOSE
 THAT ARE NOT REQUIRED TO BE ACCESSIBLE ARE NOT REQUIRED
 TO COMPLY WITH THESE REQUIREMENTS. HOWEVER, COMMON USE
 AND PUBLIC USE SPACES SUCH AS RECOVERY ROOMS,
 EXAMINATION ROOMS, AND CAFETERIAS ARE NOT EXEMPT FROM
 THESE REQUIREMENTS AND MUST BE ACCESSIBLE.
 FLORIDA VERTICAL ACCESSIBILITY REQUIRES ALL LEVELS IN
 ALL NEW BUILDINGS, STRUCTURES AND FACILITIES AND ALL
 ALTERED AREAS OF EXISTING BUILDINGS, STRUCTURES AND
 FACILITIES TO BE ACCESSIBLE TO PERSONS WITH
 DISABILITIES. ALL NEW AND ALTERED AREAS MUST COMPLY
 WITH THE ADA STANDARDS FOR ACCESSIBLE DESIGN INCLUDING
 REQUIREMENTS FOR ACCESSIBLE ROUTES. WHERE THE ADA
 STANDARDS DO NOT REQUIRE AN ACCESSIBLE ROUTE TO EACH
 AND EVERY LEVEL, THE FLORIDA REQUIREMENT MAY BE WAIVED
 DOWN TO THE REQUIREMENT OF THE ADA STANDARDS.
  
 15-3) PROVIDE AN ACCESSIBLE ROUTE TO AND THROUGH THE
 PUBLIC AREAS. FBC-A 206.1 GENERAL. ACCESSIBLE ROUTES
 SHALL BE PROVIDED IN ACCORDANCE WITH 206 AND SHALL
 COMPLY WITH CHAPTER 4.
  
 15-4) PROVIDE AN ACCESSIBLE BATHROOM.
 FBC-A 213 TOILET FACILITIES AND BATHING FACILITIES
 213.1 GENERAL.
 WHERE TOILET FACILITIES AND BATHING FACILITIES ARE
 PROVIDED, THEY SHALL COMPLY WITH 213. WHERE TOILET
 FACILITIES AND BATHING FACILITIES ARE PROVIDED IN
 FACILITIES PERMITTED BY 206.2.3 EXCEPTIONS 1 AND 2 NOT
 TO CONNECT STORIES BY AN ACCESSIBLE ROUTE, TOILET
 FACILITIES AND BATHING FACILITIES SHALL BE PROVIDED ON
 A STORY CONNECTED BY AN ACCESSIBLE ROUTE TO AN
 ACCESSIBLE ENTRANCE.
 213.2 TOILET ROOMS AND BATHING ROOMS.
 WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL
 COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH
 BATHING ROOM SHALL COMPLY WITH 603.
  
 16) THE $320,000.00 PERMIT VALUE APPEARS TO BE LOW FOR
 THE SCOPE OF THE PROPOSED PROJECT. PLEASE PROVIDE
 CONTRACTS, INVOICES, ESTIMATES ETC. THAT SHOW THE TOTAL
 COST OF THE PROJECT INCLUDING, LABOR, MATERIALS,
 EQUIPMENT, APPLIANCES, FIXTURES, DESIGN FEES, SITE
 WORK, OVERHEAD AND PROFIT- SECTION 109.3 WPB.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 17) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
  
  
  
  
  
  
  
  
  
  
  
  