2018-07-05 10:30:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE SUBMITTED PLANS APPEARS TO ONLY PROVIDE LIMITED
 INFORMATION.
  
 THERE IS A NOTE INDICATING "UP-GRADE ANSUL FIRE
 SYSTEM".
  
 PER NFPA 17A
  
 CHAPTER 6 PLANS AND ACCEPTANCE TESTS
  
 6.1.1 THE FOLLOWING ITEMS SHALL BE INCLUDED IN THE
 SPECIFICATIONS:
 (1) DESIGNATION OF THE AUTHORITY HAVING JURISDICTION
 AND INDICATION
 OF WHETHER PLANS ARE REQUIRED
 (2) STATEMENT THAT THE INSTALLATION CONFORMS TO THIS
 STANDARD
 AND MEETS THE APPROVAL OF THE AUTHORITY HAVING
 JURISDICTION
 (3) INDICATION THAT ONLY EQUIPMENT REFERENCED IN THE
 MANUFACTURER?S
 DESIGN, INSTALLATION, AND MAINTENANCE MANUAL
 OR ALTERNATIVE SUPPLIERS? COMPONENTS THAT ARE LISTED
 FOR
 USE WITH THE SPECIFIC EXTINGUISHING SYSTEM SHALL BE
 USED
 (4) IDENTIFICATION OF SPECIAL AUXILIARY DEVICES
 ACCEPTABLE TO
 THE SYSTEM MANUFACTURER AND THE AUTHORITY HAVING
 JURISDICTION
 (5) LIST OF THE SPECIFIC TESTS, IF ANY, THAT ARE
 REQUIRED
 (6) IDENTIFICATION OF THE HAZARD TO BE PROTECTED,
 INCLUDING
 SUCH INFORMATION AS PHYSICAL DIMENSIONS, COOKING
 APPLIANCES,
 ENERGY SOURCES FOR EACH APPLIANCE, AND AIRHANDLING
 EQUIPMENT
  
 6.3.2 THE PLANS SHALL CONTAIN SUFFICIENT DETAIL TO
 ENABLE THE
 AUTHORITY HAVING JURISDICTION TO EVALUATE THE
 PROTECTION OF THE
 HAZARD(S).
 6.3.3 THE DETAILS ON THE SYSTEM SHALL INCLUDE THE
 FOLLOWING:
 (1) SIZE, LENGTH, AND ARRANGEMENT OF CONNECTED PIPING
 (2) DESCRIPTION AND LOCATION OF NOZZLES
 6.3.4 INFORMATION SHALL BE SUBMITTED PERTAINING TO THE
 FOLLOWING:
 (1) THE LOCATION AND FUNCTION OF DETECTION DEVICES
 (2) OPERATING DEVICES
 (3) AUXILIARY EQUIPMENT
 (4) ELECTRICAL CIRCUITRY
  
 PLEASE PROVIDE THE ENTIRE SYSTEM COMPONENTS AND FLOWS
 AND IDENTIFY WHAT IS EXISTING AND WHAT IS
 NEW/UP-GRADING.
  
  
  
 2) THERE IS NO INDICATION THAT THE INSTALLATION WILL
 COMPLY WITH NFPA 17A PER 6.1.1 (2) ABOVE.
  
 PLEASE PROVIDE ALLPICABLE NOTE.
  
  
  
 3) THERE ARE MULTIPLE NOZZLE SPEC SHEETS ATTACHED;
 HOWEVER, THERE ARE NO INDICATIONS WHICH NOZZLES ARE
 BEING USED.
  
 PLEASE INDICATE WHICH NEW NOZZLES ARE BEING USED AND
 WHICH ONES ARE EXISTING.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL