| Plan Review Notes For Permit 18070009 |
| Permit Number |
18070009 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-07-12 11:00:05 | 1. DIAGRAM NEEDS TO INDICATE CIRCUIT NUMBER THAT | | | REPRESENTS THE CALCULATIONS OF CIRCUIT | | | 2. HIGHLIGHT TYPE OF MODULE BEING INSTALLED IN THE | | | EQUIPMENT SPEC PACKET. | | | 3. DIAGRAM DOESN?T PROVIDE ACCURATE INFO TO REFLECT | | | EACH FLOOR PLAN | | | EX.1. MISSING SMOKE DETECTOR ON THE 2ND FLOOR | | | EX.2. DIAGRAM SHOWS STROBE DEVICE FOR GROUND FLOOR | | | INSTEAD OF A MINI HORN | | | | | | 4. WHAT IS THE EDITION OF N.F.P.A 72 | | | | | | |
|