Plan Review Notes
Plan Review Notes For Permit 18061480
Permit Number 18061480
Review Stop P
Sequence Number 1
Notes
Date Text
2018-07-27 14:42:547/27/18 SEPARATED IRRIGATION APPLICATION FROM LANDSCAPE
 APPLICATION AND PLANS 18061478, AS THERE ARE NO
 IRRIGATION PLANS INCLUDED. RC
2018-07-25 13:32:311) SUBMIT TWO SETS OF PLANS FOR THE IRRIGATION SYSTEM.
 WPB AMEND. TO FBC SEC. 107.2.1.
 2) CLEARLY SHOW THE WATER SOURCE FOR THE IRRIGATION
 SYSTEM. A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE
 WATER SUPPLY PER THE CITY OF WPB CROSS CONNECTION
 CONTROL MANUAL AND 2017 FBC-PLUMBING SEC.608.1. A
 SEPARATE PLUMBING PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTER.
 3) SHOW THE TYPE AND LOCATION OF THE BACKFLOW
 PREVENTION DEVICE ON THE PLANS.WPB AMEND. TO FBC SEC.
 107.2.1.
 4) A RAIN SENSOR IS REQUIRED ON THE IRRIGATION SYSTEM
 PER FL. STATUTE 373.62.
 5) SHOW THE LOCATION OF THE CONTROLLER AND THE RAIN
 SENSOR ON THE PLANS.WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW