| 2019-04-22 10:32:11 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18061479 |
| | REVIEWED: AUGUST 13, 2018 |
| | 2ND REVIEW : APRIL 22, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO |
| | MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. |
| | CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION. |
| | PROVIDE FOR THERMAL ENVELOPE INCLUDING FLOOR SPACE. |
| | -ADDITIONAL COMMENT |
| | 103.1.1.2 FBC[RE] THE BUILDINGS OWNER, THE OWNERS |
| | ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED |
| | BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN |
| | COMPLIANCE WITH THE CODE, AS PER SECTION 553.907, |
| | FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO |
| | BEGIN CONSTRUCTION OR RENOVATION. 553.907, FLORIDA |
| | STATUTES. -PLEASE HAVE THE OWNER SIGN THE ENERGY |
| | CALCULATIONS. |
| | -ENERGY CALCULATION SAND PLANS ARE CONFLICTING. ENERGY |
| | CALCS ARE CALLING FOR WOOD FRAMING WITH R-19 AND THEY |
| | CALL FOR R-30 AT CEILING. PLANS CALL FOR MASONRY WALLS |
| | AND R-19 RIGID AT CEILING. |
| | -ENERGY CALCS SAY SLAB ON GRADE, BUT PLANS ALSO SHOW |
| | RAISED FLOOR. BOTH FLOOR TYPES SHOULD BE ON THE ENERGY |
| | CALCULATIONS. |
| | -ENERGY CALS SAY VENTED ATTIC AND PLANS ARE FOR |
| | UNVENTED. |
| | -IS RIGID BOARD INSULATION AIR-IMPERMEABLE OR |
| | AIR-PREMEABLE? COORIDINATE R VALUES BETWEEN PLANS AND |
| | ENERGY CALCULATIONS. |
| | |
| | 2. OK. |
| | |
| | 3. OK. |
| | |
| | 4. OK. |
| | |
| | 5. OK. |
| | |
| | 6. OK. |
| | |
| | 7. OK. |
| | |
| | B. [FBC 107.2.1.2] (SEE ROOFING REVIEW FOR ROOFING |
| | COMMENTS) |
| | |
| | C. OK. |
| | |
| | 8. NEW COMMENT. DRAWINGS SETS DO NOT MATCH. ONE SET IS |
| | MISSING SHEET A1.4. THE SHEET IS NOT IN THE VOIDS THAT |
| | ARE TRAVELING WITH PERMIT SETS. PLEASE ADD OR REMOVE |
| | SHEET A1.4 SO SETS MATCH AND INTENDED DRAWINGS ARE IN |
| | THE SET. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |