Plan Review Notes
Plan Review Notes For Permit 18061479
Permit Number 18061479
Review Stop B
Sequence Number 1
Notes
Date Text
2018-08-13 09:27:31****CORRECTIONS****
 W.P.B. PERMIT: 18061479
 REVIEWED: AUGUST 13, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO
 MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE.
 CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
 PROVIDE FOR THERMAL ENVELOPE INCLUDING FLOOR SPACE.
  
 2. [FBC R408.1]PROVIDE VENTING CALCULATIONS FOR UNDER
 FLOOR SPACE, OR FOLLOW REQUIREMENTS FOR UNVENTED.
  
 3. [FBC R806]SUPPLY VENTING CALCULATIONS FOR THE ATTIC
 AND HOW THE AREA OF VENTING WILL BE ACHIEVED, OR FOLLOW
 R805.5 FOR UNVENTED.
  
 4. [FBC R318]ARE EXISTING SLABS AND EXISTING 2X8 FLOOR
 JOISTS GOING TO STAY IN PLACE? HOW WILL TERMITE
 TREATMENT BE PROVIDED FOR THE ADDITION?
  
 5. [FBC EXISTING 1103]PROVIDE ENGINEERING TO SHOW THAT
 EXISTING WALL CAN SUPPORT NEW ROOF TRUSSES.
  
 6. SHEET A1.2 FIXED WINDOW IN PLAN SAYS 16? H X 72? W.
 THE SCHEDULE SAYS 12? X 72? AND THE MARK SAYS 1 WHILE
 THE PLAN SAYS 2. PLEASE UPDATE TO MATCH AND PROVIDE
 PRESSURE FOR THIS OPENING ON A2.1.
  
 7. [FBC 107.3.4.1]DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL FOR
 REVIEW, AND THEN FORWARED TO THE BUILDING OFFICIAL
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE
 INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN APPROVED BY THE BUILDING OFFICIAL.
 A. PROVIDE PRODUCT APPROVALS FOR WINDOWS, WINDOW MULL,
 DOORS, TRANSOMS, SLIDERS AND SOLAR TUBES, OR INDICATE
 THAT YOU WOULD LIKE THEM DEFFERED.
  
 B. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED.
 (SEE ROOFING REVIEW FOR ADDITIONAL ROOFING COMMENTS)
  
 C. [FBC 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS, OR
 INDICATE THAT THE SUBMITTAL WILL BE DEFERRED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  