Plan Review Notes
Plan Review Notes For Permit 18061475
Permit Number 18061475
Review Stop P
Sequence Number 1
Notes
Date Text
2018-08-07 16:04:2508/07/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON P-02 ON YOUR ISOMETRIC DRAWING THE WASHING
 MACHINE DRAIN CANNOT COME OFF THE LAV ARM INTO A DOUBLE
 SANITARY TEE 2017 FBC R3005.1.1 HORIZONTAL TO VERTICAL
 (MULTIPLE CONNECTION FITTINGS), IT MAY COME OFF THE
 TRUNK LINE DOWNSTREAM FROM BATHROOM GROUP IN MOST
 WASHING MACHINE IT MAY REQUIRE A 3? DRAIN PER
 MANUFACTURES SPECIFICATION.
 2. WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR
 SHUTTING OFF WITHOUT MOVING UNITS, 2017 FBC SEC
 R2903.9.3 FIXTURE VALVES AND ACCESS. ACCESSIBLE,
 SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL OF AN ACCESS
 PANEL OR SIMILAR REMOVABLE OBSTRUCTION.
 3. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A
 WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS
 OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN
 ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB
 AND WHIRLPOOL BATHTUB VALVES.
 4. THE ADJOINING WALLS AND FLOOR FRAMING ENCLOSING
 ON-SITE BUILT-UP SHOWER RECEPTORS SHALL BE LINED WITH
 ONE OF THE FOLLOWING MATERIALS:
 PLASTIC LINER MATERIAL THAT COMPLIES WITH ASTM D4068 OR
 ASTM D4551.
  
 THE LINING MATERIAL SHALL EXTEND NOT LESS THAN 2 INCHES
 (51 MM) BEYOND OR AROUND THE ROUGH JAMBS AND NOT LESS
 THAN 2 INCHES (51 MM) ABOVE FINISHED THRESHOLDS.
 SHEET-APPLIED LOAD BEARING, BONDED WATERPROOF MEMBRANES
 SHALL BE APPLIED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS.
  
 NOTE: SHOWER PAN MUST HAVE A SLOPED MORTAR BED THAT IS
 PRE-PITCHED BENEATH PRIOR TO LINER INSTALLATION OF 1/4"
 IN PER FOOT TOWARD THE DRAIN, MUST HAVE DAM CORNER,
 BACKING AROUND THE PERIMETER AND BEFORE FINAL MORTAR
 APPLICATION PLACE SOME PEA GRAVEL OVER WEEP HOLES SO
 THE MORTAR DOES NOT COVER THEM PER MANUFACTURES
 SPECIFICATIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  