Plan Review Notes
Plan Review Notes For Permit 18061475
Permit Number 18061475
Review Stop G
Sequence Number 1
Notes
Date Text
2018-08-07 15:18:4908/07/2018 1ST GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC
 SEC. 107.3.5.3 (12) RESIDENTIAL GAS. PLEASE SUBMIT AN
 ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL
 CUT SECTIONS OF PIPE PER 2017 FBC FUEL GAS RES SECS.
 G2413.4.1, G2413.4.2.
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 3. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 4. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS RES. SEC.
 G2420.4.
 5. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION, 2017 FBC FUEL GAS RES. SEC. G2421.1.
 6. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC FUEL GAS
 RES. SEC. G2413.
 7. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 RANGE, 2017 FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4.
 8. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC FUEL GAS RES. SEC. G2413.2.
 9. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL GAS RES.
 SECS. G2426 THRU G2429.1
 10. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2017 FBC FUEL GAS RES. SEC.
 G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3
 11. SUBMIT TWO COPIES MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT
 (FIREPLACE, TANKLESS AND RANGE) TO VERIFY COMPLIANCE
 WITH 2017 FBC FUEL GAS RES. SEC. G2408.1.
 12. SUBMIT TWO COPIES OF DETAIL SHOWING THE TYPE,
 LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE THE
 ROOF AND ANCHORING DETAILS OF THE GAS VENT FOR
 FIREPLACE PER 2017 FBC FUEL GAS SECS. 502 THRU 505 OR
 2017 FBC FUEL GAS RES. SECS. G2426 THRU G2429.1
 13. FIRE PLACE MANUFACTURES INSTALLATION INSTRUCTION
 SHALL BE ON SITE AT TIME OF INSTALLATION.
 14. ON BOTH COPIES OF A HOUSE PLAN SHOW THE LOCATION OF
 THE TANKLESS WATER HEATER AND THE LOCATION AND DISTANCE
 OF ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE
 WATER HEATER. THE LOCATION OF THE WATER HEATER SHALL
 COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 15. SUBMIT TWO COPIES MANUFACTURER?S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION, WHERE APPLICABLE AND SHALL BE ON SITE,
 2017 FBC FUEL GAS RES. SEC. G2421.1.
 16. A ELECTRICAL OUT MAY BE REQUIRED FOR SOURCE OF
 IGNITION, WPB AMENDMENTS TO THE FBC SEC 105.1
 17. A SEPARATE GAS PERMIT SHALL BE REQUIRED, FBC WPB A
 107.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  