| 2018-10-03 12:24:32 | 10/03/18 READ E-MAIL FROM GERI SHUBERT. |
| | |
| | HAVE A GREAT DAY |
| | GERI SHUBERT |
| | DIVERSIFIED ROOFING SOLUTIONS, INC |
| | 450 SOUTH OLD DIXIE HWY #1 |
| | JUPITER, FL 33458 |
| | 561-841-5676 |
| | |
| | |
| | |
| | |
| | THIRD BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017). |
| | |
| | NOTE: |
| | IT IS NOT CLEAR WHY SUBMITTING A TWO STORY WALL |
| | SECTION. THE ITEMS BELOW ARE THE ONES THAT NEED TO BE |
| | ADDRESSED. PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS, |
| | SO WE CAN FINISH PROCESSING THIS PERMIT. NOTE: ROOF TO |
| | WALL WORK NEED TO BE DONE UNDER A SUBPERMIT. ACCORDING |
| | TO ROBERT (BROWN (BUILDING OFFICIAL) ROOFING CONTRACTOR |
| | CAN NOT DO THIS WORK UNLESS LICENSE TO DO SO. |
| | |
| | |
| | |
| | PLAN REVIEW COMMENTS: |
| | 1- IT LOOKS LIKE THE HOUSE WAS DESIGNED FOR SHINGLES AS |
| | A ROOF COVERING. PROPOSED ROOFING MATERIAL IS CONCRETE |
| | TILES. PROVIDE ENGINEERING ANALYSIS SHOWING THAT THE |
| | EXISTING STRUCTURE IA CAPABLE OF SUPPORTING THE |
| | ADDITIONAL LOAD. SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 2- HOUSE VALUE IS MORE THAN $300.000. NEED TO COMPLY |
| | WITH THE ROOF TO WALL CONNECTIONS AS REQUIRED BY SEC. |
| | 706.8 FBC-EXISTING-BUILDING. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | SEC. 706.8: |
| | WHEN A ROOF COVERING ON AN EXISTING SITE-BUILT |
| | SINGLE-FAMILY RESIDENTIAL STRUCTURE IS REMOVED AND |
| | REPLACED ON A BUILDING THAT IS LOCATED IN THE |
| | WIND-BORNE DEBRIS REGION AS DEFINED IN THE FLORIDA |
| | BUILDING CODE, BUILDING AND THAT HAS AN INSURED VALUE |
| | OF $300,000 OR MORE OR, IF THE BUILDING IS UNINSURED OR |
| | FOR WHICH DOCUMENTATION OF INSURED VALUE IS NOT |
| | PRESENTED, HAS A JUST VALUATION FOR THE STRUCTURE FOR |
| | PURPOSES OF AD VALOREM TAXATION OF $300,000 OR MORE: |
| | (A)ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS |
| | REQUIRED BY SECTION 706.8.1. |
| | (B)MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION |
| | SHALL NOT BE REQUIRED BEYOND A 15 PERCENT INCREASE IN |
| | THE COST OF REROOFING. |
| | EXCEPTION: SINGLE-FAMILY RESIDENTIAL STRUCTURES |
| | PERMITTED SUBJECT TO THE FLORIDA BUILDING CODE ARE NOT |
| | REQUIRED TO COMPLY WITH THIS SECTION. |
| | |
| | 3- NEW FLAT ROOF NOA 15-0622.21 AND ENGINEER RAS 117 |
| | CALCULATIONS SUBMITTED ARE OK. NEED TO PROVIDE TWO |
| | COPIES OF ENGINEER CALCULATIONS WITH ENGINEER'S |
| | ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 |
| | WHEN ENGINEER IS SUBMITTING DOCUMENTS FOR PUBLIC |
| | RECORDS. |
| | |
| | NEW COMMENTS: |
| | 4- NEW ROOF TILE PRODUCT APPROVAL WAS SUBMITTED. ONLY |
| | THE COVER PAGES OF FLORIDA PRODUCT APPROVAL FL7849-R11 |
| | WAS SUBMITTED. NEED TO PROVIDE COMPLETE INSTALLATION |
| | INSTRUCTIONS FOR SPECIFIC ROOF TILE TO BE INSTALLED. |
| | AND CLEARLY SPECIFY/MARK ADHESIVE PADDY SIZE AND RIDGE |
| | MATERIAL TO BE USED. PROVIDE 2 COPIES. |
| | FAC 61G20-3.001. |
| | |
| | 5- NEW ROOF TILE ADHESIVE PRODUCT APPROVAL WAS |
| | SUBMITTED. ONLY THE COVER PAGES OF FLORIDA PRODUCT |
| | APPROVAL FL6332-R8 WAS SUBMITTED. NEED TO PROVIDE |
| | COMPLETE INSTALLATION INSTRUCTIONS AND CLEARLY |
| | SPECIFY/MARK ADHESIVE PADDY SIZE AND RIDGE MATERIAL ON |
| | PAGES 3 AND 4 OF INSTALLATION INSTRUCTIONS. PROVIDE 2 |
| | COPIES. |
| | FAC 61G20-3.001. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |