| 2018-08-03 08:08:13 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18061434 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. [FBC 107.3.5.3] PROVIDE SEDIMENT CONTROL PLAN TO |
| | KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT |
| | PROPERTIES AND STORM DRAINS. |
| | |
| | 2. [FBC R403.1.7.3] FOUNDATION ELEVATION. ON GRADED |
| | SITES, THE TOP OF ANY EXTERIOR FOUNDATION SHALL EXTEND |
| | ABOVE THE ELEVATION OF THE STREET GUTTER AT POINT OF |
| | DISCHARGE OR THE INLET OF AN APPROVED DRAINAGE DEVICE A |
| | MINIMUM OF 12 INCHES (305 MM) PLUS 2 PERCENT. ALTERNATE |
| | ELEVATIONS ARE PERMITTED SUBJECT TO THE APPROVAL OF THE |
| | BUILDING OFFICIAL, PROVIDED IT CAN BE DEMONSTRATED THAT |
| | REQUIRED DRAINAGE TO THE POINT OF DISCHARGE AND AWAY |
| | FROM THE STRUCTURE IS PROVIDED AT ALL LOCATIONS ON THE |
| | SITE. |
| | |
| | 3. [FBC R401.3]PROVIDE SITE DRAINAGE PLAN. WATER IS TO |
| | BE MANAGED ON SITE AND IS NOT TO DRAIN INTO ADJACENT |
| | PROPERTIES. |
| | |
| | 4. [FBC R401.4]PROVIDE SOIL REPORT.-NOT REQUIRED FOR |
| | THIS PROJECT DB-10-24-18 |
| | |
| | 5. [FBC R2319.17.2.1.1]PREFABRICATED WOOD TRUSSES SHALL |
| | BE DESIGNED BY A REGISTERED ENGINEER. |
| | |
| | 6. [FBC 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS, OR |
| | INDICATE THAT THE SUBMITTAL WILL BE DEFERRED. DEFERRED |
| | SUBMITTALS TO BE REVIEWED PRIOR TO INSTALLATION. |
| | |
| | 7. ARE YOU ISOLATING THE FRONT AND REAR PATIO FROM THE |
| | MAIN HOUSE WITH ICYNENE? WHAT WILL BE THE THERMAL |
| | BARRIER, 1/2 DRYWALL? SHOW ON PLANS HOW INSULATION |
| | FILLS FROM ROOF DECK TO BEAM BELOW AND WHAT THE |
| | INSULATION ATTACHES TO. ALSO, SEE FOLLOWING COMMENT |
| | ABOUT ATTIC ACCESS. |
| | |
| | 8. [FBC R807]BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF |
| | CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING TO |
| | ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF 30 INCHES OR |
| | GREATER OVER AN AREA OF NOT LESS THAN 30 SQUARE FEET. |
| | |
| | 9. WHAT IS HAPPENING BETWEEN THE HOUSE AND GARAGE WITH |
| | THE THERMAL ENVELOPE? PLANS SHOW ICYNENE AT THE GARAGE |
| | ROOF AND INSULATION AT WALL IN BETWEEN HOUSE AND |
| | GARAGE. WHAT HAPPENS AT GARAGE CEILING AND IN BETWEEN |
| | GARAGE/HOUSE FROM ROOF DECK TO BEAM BELOW? |
| | |
| | 10. PLEASE RE-PRINT THE FOLLOWING PRODUCT APPROVALS FOR |
| | THE DRAWING PORTION THAT SHOULD BE PRINTED IN LANDSCAPE |
| | FORMAT. MUCH OF THE DATA, INCLUDING DESIGN |
| | PRESSURES/ATTACHMENT, IS CUT OFF. |
| | 18-0503.06, 18-0529.03, 17-1212.13, 17-1212.22 AND |
| | 17-1212.21 |
| | |
| | 11. PROVIDE PRODUCT APPROVAL FOR THE ATTACHMENT OF |
| | CEMENT ROOF TILE, OR INDICATE THAT IT WILL BE DEFFERED. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |