Plan Review Notes
Plan Review Notes For Permit 18061379
Permit Number 18061379
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-07-10 12:25:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 1) THESE SHOP DRAWINGS HAVE A PE STAMP AND SEAL. I
 COULD NOT VERIFY IF THIS PE WAAS THE SAME ONE AS THE
 MASTER. CALLED TO VERIFY WITH THE PHONE OUT OF SERVICE
 AND NO RESPONSE TO EMAIL X 10 DAYS.
  
 THERE CAN ONLY BE ONE PE RESPONSIBLE FOR THE ENGINEERED
 DRAWINGS UNLESS EXPRESSLY DELEGATED BY THE MASTER PE.
  
 VERIFY THE SAME PE OF REMOVE STAMP AND SEAL.
  
  
  
 2) THERE IS FIRE LINE UNDERGROUND INDICATED; HOWEVER, I
 COULD NOT VERIFY FL CONTRACTOR I, II OR V ON THE STATE
 WEBSITE. CALLED TO VERIFY WITH THE PHONE OUT OF SERVICE
 AND NO RESPONSE TO EMAIL X 10 DAYS.
  
 PROVIDE VALID FL LICENSE FOR UNDERGROUND CONTRACTOR
 WORK.
  
  
  
 3) A REMOTE AREA 1 IS INDICATED ON THE HYDRAULIC SHEET;
 HOWEVER, IT IS NOT INDICATED ON THE PLAN DRAWINGS.
  
 PROVIDE THE LOCATION AND DIMENSIONS OF THE REMOTE AREA
 1 ON THE DRAWING SHEETS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  