| Plan Review Notes For Permit 18061379 |
| Permit Number |
18061379 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-07-10 12:25:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | | | | 1) THESE SHOP DRAWINGS HAVE A PE STAMP AND SEAL. I | | | COULD NOT VERIFY IF THIS PE WAAS THE SAME ONE AS THE | | | MASTER. CALLED TO VERIFY WITH THE PHONE OUT OF SERVICE | | | AND NO RESPONSE TO EMAIL X 10 DAYS. | | | | | | THERE CAN ONLY BE ONE PE RESPONSIBLE FOR THE ENGINEERED | | | DRAWINGS UNLESS EXPRESSLY DELEGATED BY THE MASTER PE. | | | | | | VERIFY THE SAME PE OF REMOVE STAMP AND SEAL. | | | | | | | | | | | | 2) THERE IS FIRE LINE UNDERGROUND INDICATED; HOWEVER, I | | | COULD NOT VERIFY FL CONTRACTOR I, II OR V ON THE STATE | | | WEBSITE. CALLED TO VERIFY WITH THE PHONE OUT OF SERVICE | | | AND NO RESPONSE TO EMAIL X 10 DAYS. | | | | | | PROVIDE VALID FL LICENSE FOR UNDERGROUND CONTRACTOR | | | WORK. | | | | | | | | | | | | 3) A REMOTE AREA 1 IS INDICATED ON THE HYDRAULIC SHEET; | | | HOWEVER, IT IS NOT INDICATED ON THE PLAN DRAWINGS. | | | | | | PROVIDE THE LOCATION AND DIMENSIONS OF THE REMOTE AREA | | | 1 ON THE DRAWING SHEETS. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|