| 2018-07-26 14:14:33 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET FA 2 - THERE IS A HEAT DETECTOR INDICATED IN |
| | EACH KITCHEN. THE TEMPATURE RATING APPEARS TO BE 135* . |
| | |
| | WITH THE BUILDIDNG PROTECTED THROUGHOUT WITH FIRE |
| | SPRINKLERS: |
| | |
| | A) WHAT IS THE TEMPURATURE OF THE FIRE SPRINKLER IN |
| | THIS AREA? |
| | |
| | B) WHAT IS THE PURPOSE OF THIS HEAT DETECTOR? |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS AND JUSTIFICATION FOR |
| | PLACING THE HD IN THE KITCHEN. |
| | |
| | |
| | |
| | |
| | 2) SHEET FA 2 - THERE IS ONLY ONE SD INDICATED IN THE |
| | MIDDLE OF TWO BEDROOMS. THOUGH THERE IS ONE DOOR |
| | LEADING TO THESE BEDROOMS AREAS THERE ARE TWO DISTICT |
| | AND SEPARATED BEDROOMS. |
| | |
| | PER NFPA 101, CHAPTER 32 NEW RESIDENTIAL BOARD AND CARE |
| | OCCUPANCIES |
| | |
| | 32.2.3.4.3.4 EACH SLEEPING ROOM SHALL BE PROVIDED WITH |
| | AN |
| | APPROVED SMOKE ALARM IN ACCORDANCE WITH 9.6.2.10. |
| | |
| | WHERE THE ROOMS ARE SEPARATED BY WALLS INTO TWO |
| | SEPARATE SLEEPING AREAS, EACH AREA SHALL HAVE A SD. |
| | |
| | |
| | |
| | 3) FIRE SPRINKLER HYDRAULIC PLANS WERE INCLUDED WITH |
| | THE PLAN SETS AND NOT REPLATED TO THE PERMIT |
| | APPLICATION. |
| | |
| | PLEASE REMOVE THEM FROM THE PALN SET OF JUSTIFY . |
| | |
| | |
| | |
| | |
| | 4) SHEET FA 2 - THERE IS ONLY A HD INDICATED IN |
| | THELAUNDRY ROOM. |
| | |
| | WITH THE BUILDIDNG PROTECTED THROUGHOUT WITH FIRE |
| | SPRINKLERS: |
| | |
| | A) WHAT IS THE TEMPURATURE OF THE FIRE SPRINKLER IN |
| | THIS AREA? |
| | |
| | B) WHAT IS THE PURPOSE OF THIS HEAT DETECTOR? |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS AND JUSTIFICATION FOR |
| | PLACING THE HD IN THE LAUNDRY ROOM |
| | |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |