Plan Review Notes
Plan Review Notes For Permit 18061371
Permit Number 18061371
Review Stop E
Sequence Number 2
Notes
Date Text
2018-09-26 08:29:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED, SHOWN ON PERMIT 15070145.
 5. CORRECTED, SHOWN ON PERMIT 15070145.
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 (NOTE 3
 ON SHEET E-3 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14)
 7. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16 (NOTE 2 ON
 SHEET E-3 DOES NOT INCLUDE THE ALL AREAS REQUIRED TO BE
 AFCI PROTECTED. PROVIDE CORRECTION.)
 8. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1 (THIS NOTE WAS ADDED TO SHEET
 E-2, BUT A CONFLICTING NOTE EXIST ON SHEET E-3. CORRECT
 DISCREPANCY. WPB FBC 107.2.1)
 9. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 (LOAD CALCULATION WAS PROVIDED ONLY FOR GARAGE PANEL,
 NOT ENTIRE SERVICE. BE ADVISED THAT DEMAND FACTORS USED
 CANNOT BE APPLIED TO THE GARAGE PANEL AS IT IS NOT FEED
 BY A 100 AMP FEEDER. NEC 220.82; FBC RE3602.2.1.
 ADDITIONALLY, UPON RESEARCHING PERMIT 15070145, I SEE
 THAT THE STATED LOAD ON THE SERVICE IS 175 AMPS, WITH
 10 AMPS INCLUDED FOR THE GARAGE. NOW, WITH THE
 ADDITIONAL LOAD OF THE GARAGE, BASED ON THESE NUMBERS
 AND THE PROPER CALCULATION FOR THE GARAGE PANEL, THE
 SERVICE WILL BE OVERLOADED. PROVIDE CORRECTION AND
 PROVIDE ACCURATE LOAD CALCULATION AS PREVIOUSLY
 REQUESTED. NEC 220; FBC RE 3602)
 10. CORRECTED.
  
 NEW COMMENT:
  
 11. AN ARCHITECT HAS SIGNED AND SEALED THE "E" SHEETS.
 PROVIDE CORRECTION. FS 471.003(2)(H), 471.025; WPB FBC
 107.1
 12. THE CABANA MEETS THE DEFINITION OF A BEDROOM IN THE
 FLORIDA STATUTES AND SHOULD HAVE A SMOKE ALARM
 INSTALLED. FS 381.0065; FBC RE R314.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER