| Plan Review Notes For Permit 18061330 |
| Permit Number |
18061330 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-07-10 17:12:07 | 07/10/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. YOUR PLAN ARE DESIGNED BASED ON 2014 FBC 5TH | | | EDITION, PLEASE REFLECT THE 2017 FBC 6TH EDITION, WPB | | | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | 2. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION, 2017 FBC FUEL GAS RES. SEC. G2421.1 | | | | | | 3. A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | | IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL | | | GAS RES. SEC. G2420.4. | | | | | | SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY | | | RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING, | | | IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING | | | EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED | | | SHEETS. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|