| Notes |
| Date |
Text |
| 2018-07-30 07:27:17 | 07/29/2018 1ST PLUMBING/GAS REVIEW **DENIED** WITH | | | COMMENTS. | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. SECOND REQUEST, SUBMIT MANUFACTURES SPECIFICATIONS | | | FOR THE GENERATOR AND MANUFACTURER'S SPECIFICATIONS FOR | | | THE GENERATOR SHALL BE ONSITE FOR FINAL GAS INSPECTION. | | | THE GENERATOR SHALL BE LISTED AND APPROVED. NFPA 58 | | | SEC. 5.20.1. THE GENERATOR SHALL MEET THE REQUIREMENTS | | | OF UL 2200. 2017 FBC FUEL GAS SEC.305.1. | | | 2. SECOND REQUEST, SUBMIT TWO COPIES OF THE SIZING | | | TABLE AFTER PE THAT IS USED IN THE DESIGN FOR THE GAS | | | SYSTEM OR PLACE A NOTE ON BOTH SETS OF PLANS LISTING | | | THE SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD | | | THAT WERE USED IN THE DESIGN OF THIS SYSTEM, THE ONE | | | SUMMITED ARE NOT PE2017 FBC FUEL GAS SEC. 402.3. | | | | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | | | | | | | |
|