| 2018-07-30 15:09:24 | 07/30/2018 2ND PLUMBING/GAS REVIEW **DENIED** WITH |
| | COMMENTS. |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. YOUR ISOMETRIC DRAWING THE TANKLESS WATER HEATER IS |
| | 199 BTU AND ON YOUR TECHNICAL DATA V65E IS 150 BTU, |
| | PLEASE CORRECT AD RESIZE YOUR TOTAL LOAD. WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 2. SECOND REQUEST, SUBMIT COMBUSTION AIR CALCULATIONS |
| | FOR THE ADDED GAS APPLIANCES. WHERE IS COMBUSTION AIR |
| | PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION |
| | SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED |
| | COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED |
| | VENTILATION AIR? THIS WILL BE REVIEWED AS A NEW SYSTEM. |
| | 2017 FBC R G2407.9.3. COMBINED COMBUSTION AIR AND |
| | VENTILATION AIR SYSTEM. |
| | 3. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. (CSST, PE PIPE) REFER TO THE |
| | 2017 FBC FUEL GAS SECS. G2412.4, G2412.8, G2413.1, |
| | G2413.2, & G2413.3. |
| | 4. SECOND REQUEST, SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS RES. SEC. |
| | G2408.1. ( POOL HEATER, RANGE AND DRYER?ECT) |
| | 5. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL |
| | GAS RES. SEC. G2413.2 AND G2404.3. |
| | 6. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE |
| | OF IGNITION, WPB AMENDMENTS TO THE FBC SEC 105.1 |
| | 7. SHOW SHUTOFF VALVE ON GAS ISOMERIC AT EACH APPLIANCE |
| | PLEASE, 2017 FBC FUEL GAS RES. SEC. 409.5, APPLIANCE |
| | CONNECTION 2017 FBC FUEL GAS RES. SEC. 404.15, 411. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |