Plan Review Notes
Plan Review Notes For Permit 18061260
Permit Number 18061260
Review Stop P
Sequence Number 1
Notes
Date Text
2018-08-22 19:55:2208/22/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ISOMETRIC SHOWS KITCHEN SINK TIED TO A BATHROOM
 GROUP, IT SHALL RUN DOWNSTREAM OF THE BATHROOM GROUP.
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 2. RELIEF LINE SHALL DUMP INTO PAN DRAIN AND PAN DRAIN
 SHALL TERMINATE OUTSIDE. 2017 FBC R 2801.6.2
 3. THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE LINING
 FBC R 2709.2 LINING REQUIRED.
  
 NOTE: SHOWER PAN MUST HAVE A SLOPED MORTAR BED THAT IS
 PRE-PITCHED BENEATH PRIOR TO LINER INSTALLATION OF 1/4"
 IN PER FOOT TOWARD THE DRAIN, MUST HAVE DAM CORNER,
 BACKING AROUND THE PERIMETER AND BEFORE FINAL MORTAR
 APPLICATION PLACE SOME PEA GRAVEL OVER WEEP HOLES SO
 THE MORTAR DOES NOT COVER THEM PER MANUFACTURES
 SPECIFICATIONS.
  
 4. THE WATER HEATER ON YOUR FLORIDA ENERGY EFFICIENCY
 FORM R405-2017 IS SHOWING THE E.F AS .92. AS OF APRIL
 16, 2015, ALL RESIDENTIAL WATER HEATERS ARE REQUIRED TO
 BE A MIN .95 E.F UP TO 55 GALLONS. THIS IS DEFINED IN
 THE CODE OF FEDERAL REGULATION (CFR) 75 FR 2012. NEACA
 HOT WATER REGULATION 2015 AND IT SHOULD BE AT EF 0.95,
 PLEASE VISIT HTTP://WWW.CASHACME.COM/RESOURCES/NAECA-20
 15-REGULATIONS/ FOR FURTHER DETAILS.
  
 5. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST
 PALM BEACH ORD #2853-95. PLEASE CONTACT CITY OF WPB
 UTILITIES AT 561-822-2240 FOR FURTHER DIRECTIONS. A
 BACKFLOW DEVICE MAY BE REQUIRED BY THE CITY OF WEST
 PALM BEACH UTILITY DEPARTMENT CROSS CONNECTION MANUAL.
 A PERMIT REQUIRED BY A LICENSED CONTRACTOR AND
 APPLICATION ALONG WITH CERTIFICATION BY UTILITIES WITH
 A FINAL INSPECTION WILL BE REQUIRED. CALL THE UTILITY
 DEPARTMENT FOR INFORMATION AT 561 822-2240.
  
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved