| 2018-07-10 06:11:28 | 1) SHOW THE TYPE OF PIPING FOR THE GAS SYSTEM ON THE |
| | PLANS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 2)THE EXISTING GAS PLAN ON RECORD WITH THE CITY SHOWS |
| | THE DEVELOPED LENGTH AS 52 FEET TO THE FARTHEST OUTLET. |
| | THE SUBMITTED PLAN SHOWS 40 FEET DEVELOPED LENGTH.THE |
| | 52 FEET LENGTH SHALL BE USED FOR THE DESIGN OF THIS |
| | SYSTEM. 2017 FBCR SEC. G2413.4.1. |
| | 3) THE EXISTING PLAN ON RECORD WITH THE CITY SHOWS CSST |
| | PIPING OVERHEAD WITHIN THE STRUCTURE. SHOW THIS ON THE |
| | SUBMITTED PLAN IF IT IS ACTUALLY INSTALLED IN THE |
| | FIELD. |
| | 4) SUBMIT TWO COPIES OF THE SIZING TABLE FOR THE CSST |
| | AND THE CORRESPONDING EHD NUMBER OF THE CORRUGATED |
| | STAINLESS STEEL TUBING FOR EACH PIPE SIZE. WPB |
| | AMENDMENTS TO FBC SEC.107.2.1. |
| | 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS AND ALSO |
| | SOFFIT VENTS IN RELATION TO THE WATER HEATER. THE |
| | LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE |
| | PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 6) THE EXISTING GAS PLAN ON FILE WITH THE CITY IS |
| | DESIGNED ON A PRESSURE DROP OF A 0.5 INCH WATER COLUMN |
| | YET THE SUBMITTED TABLE IS FOR A 6.0 INCH WATER COLUMN |
| | PRESSURE DROP.CLARIFY. |
| | 7) INDICATE THE PSI OF THIS SYSTEM ON THE GAS PLANS. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |