Plan Review Notes
Plan Review Notes For Permit 18061230
Permit Number 18061230
Review Stop B
Sequence Number 2
Notes
Date Text
2018-07-10 15:34:07PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MAXIMUM DESIGN PRESSURE FOR SYSTEM TYPE E(1)
 LISTED ON PAGE 47 OF NOA NO. 17-0824.09 IS -52.5 PSF.
 THIS IS NOT ADEQUATE FOR ROOF ZONES 2 AND 3. SUBMIT TWO
 SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER 7
 ON PAGE 63 OF THE PRODUCT APPROVAL FOR THE INCREASED
 THE UPLIFT PRESSURES OF ROOF ZONES 2 AND 3,