| Permit Number |
18061230 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-07-10 15:34:07 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE MAXIMUM DESIGN PRESSURE FOR SYSTEM TYPE E(1) | | | LISTED ON PAGE 47 OF NOA NO. 17-0824.09 IS -52.5 PSF. | | | THIS IS NOT ADEQUATE FOR ROOF ZONES 2 AND 3. SUBMIT TWO | | | SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER 7 | | | ON PAGE 63 OF THE PRODUCT APPROVAL FOR THE INCREASED | | | THE UPLIFT PRESSURES OF ROOF ZONES 2 AND 3, |
|