| Plan Review Notes For Permit 18061230 |
| Permit Number |
18061230 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-07-03 14:45:54 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PRODUCT APPROVALS FOR THE ASPHALT SHINGLES (NOA | | | NO.14-1022.21) EXPIRED ON 4/22/18. SUBMIT THE CURRENT | | | NOA FOR THE GAF SHINGLES. FBC 107.3.4 | | | | | | 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5). PROVIDE | | | TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS | | | INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN | | | PRESSURES FOR THE FLAT ROOF COVERING MATERIALS. IF | | | ENHANCED FASTENING IS REQUIRED TO INCREASE THE UPLIFT | | | PRESSURES FOR ROOF ZONES 2 AND 3, SUBMIT SIGNED AND | | | SEALED RAS 117 CALCULATIONS. | | | | | | 3) SPECIFY THE SQUARE FOOTAGE OF THE SLOPED ROOF AND | | | THE FLAT ROOF. FBC 107.2.1 |
|