| 2018-07-20 09:26:14 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. LOCATION OF ACCESSIBLE PARKING SPACES SHALL BE |
| | LOCATED ON THE SHORTEST ROUTE FROM THE PARKING SPACE TO |
| | THE BUILDING ENTRANCE PER FBC A208.3. |
| | PARKING FACILITIES SHALL COMPLY WITH 208.3 |
| | |
| | 208.3.1 GENERAL. |
| | DESIGNATED ACCESSIBLE SPACES SHALL BE DESIGNED AND |
| | MARKED FOR THE EXCLUSIVE USE OF THOSE INDIVIDUALS WHO |
| | HAVE A SEVERE PHYSICAL DISABILITY AND HAVE PERMANENT OR |
| | TEMPORARY MOBILITY PROBLEMS THAT SUBSTANTIALLY IMPAIR |
| | THEIR ABILITY TO AMBULATE AND WHO HAVE BEEN ISSUED |
| | EITHER A DISABLED PARKING PERMIT UNDER S. 316.1958 OR |
| | S. 320.0848 OR A LICENSE PLATE UNDER S. 320.084, S. |
| | 320.0842, S. 320.0843, OR S. 320.0845. PARKING SPACES |
| | COMPLYING WITH 502 THAT SERVE A PARTICULAR BUILDING OR |
| | FACILITY SHALL BE LOCATED ON THE SHORTEST ACCESSIBLE |
| | ROUTE FROM PARKING TO AN ENTRANCE COMPLYING WITH 206.4. |
| | ALL SPACES MUST BE LOCATED ON AN ACCESSIBLE ROUTE THAT |
| | IS AT LEAST 44 INCHES (1118 MM) WIDE AND SO THAT USERS |
| | ARE NOT COMPELLED TO WALK OR WHEEL BEHIND PARKED |
| | VEHICLES EXCEPT BEHIND HIS OR HER OWN VEHICLE. WHERE |
| | PARKING SERVES MORE THAN ONE ACCESSIBLE ENTRANCE, |
| | PARKING SPACES COMPLYING WITH 502 SHALL BE DISPERSED |
| | AND LOCATED ON THE SHORTEST ACCESSIBLE ROUTE TO THE |
| | ACCESSIBLE ENTRANCES. IF THERE ARE MULTIPLE ENTRANCES |
| | FOR MULTIPLE RETAIL STORES THE PARKING SPACES MUST BE |
| | DISPERSED TO PROVIDE PARKING AT THE NEAREST ACCESSIBLE |
| | ENTRANCE. IN PARKING FACILITIES THAT DO NOT SERVE A |
| | PARTICULAR BUILDING OR FACILITY, PARKING SPACES |
| | COMPLYING WITH 502 SHALL BE LOCATED ON THE SHORTEST |
| | ACCESSIBLE ROUTE TO AN ACCESSIBLE PEDESTRIAN ENTRANCE |
| | OF THE PARKING FACILITY. |
| | |
| | 2. PROVIDE ACCESSIBLE ROUTE PER FBC A206. |
| | 206.2.1SITE ARRIVAL POINTS. |
| | AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN |
| | THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE |
| | PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS; |
| | AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE |
| | BUILDING OR FACILITY ENTRANCE THEY SERVE. |
| | |
| | 3. HEIGHT TO BOTTOM OF ACCESSIBLE PARKING SIGN HAS BEEN |
| | CHANGED FROM 84 INCHES TO 60 INCHES. A COPY OF THE NEW |
| | PARKING DETAIL HAS BEEN PROVIDED FOR YOUR REVIEW AND |
| | USE. |
| | |
| | 4. VALUE - IF THE LANDSCAPE BUFFER IS TO BE INCREASED |
| | IN SIZE PER THE ZONING REVIEW COMMENT THEN THE VALUE |
| | SHALL BE ADJUSTED TO REFLECT THIS ADDITIONAL WORK. |
| | CITY OF WPB CHPT. 1 ? VALUE |
| | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF |
| | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS |
| | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE |
| | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION |
| | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION |
| | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), |
| | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. |
| | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| | BUILDING OFFICIAL. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| | |
| | |
| | |
| | |