| Plan Review Notes For Permit 18061182 |
| Permit Number |
18061182 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-26 12:57:01 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PROJECT IS LOCATED IN A 170 MPH VULT WINDSPEED | | | AND EXPOSURE CATEGORY D (CLEAR LAKE). THE FASTENING | | | OPTION #4 FOR SYSTEM TYPE A(1) THAT WAS SELECTED ON | | | PAGE 9 OF NOA NO. 15-1020.01 HAS A MAXIMUM DESIGN | | | PRESSURE OF -60 PSF. THIS DESIGN PRESSURE IS NOT | | | ADEQUATE FOR THE PERIMETER AND CORNER ROOF AREAS. | | | SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY LIMITATION NUMBER 7 ON PAGE 67 OF THE | | | PRODUCT APPROVAL. FBC 107.2.1 | | | |
|