Plan Review Notes
Plan Review Notes For Permit 18061155
Permit Number 18061155
Review Stop E
Sequence Number 1
Notes
Date Text
2018-07-11 06:19:28ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE CLEAR LOCATION OF ELECTRICAL PANEL. PANEL
 APPEARS TO BE IN CLOSET ALONG WITH W/H AND AHU. PANEL
 APPEARS TO NOT HAVE THE REQUIRED WORKING CLEARANCE TO
 MEET NEC 110.26A1 & A2.
  
 2. PROVIDE RISER DIAGRAM OF EXISTING SERVICE.
 OVERCURRENT PROTECTION, WIRE AND CONDUIT SIZE FOR
 EXISTING PANEL IN UNIT. NEC 215.5; WPB FBC 107.2.1
 VOLTAGE AT TRUMP TOWER IS BELIEVED TO BE 208V NOT 240V,
 WHICH WOULD CHANGE THE LOAD CALCULATION FROM 132.45AMPS
 TO 153AMPS
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.