Plan Review Notes
Plan Review Notes For Permit 18061145
Permit Number 18061145
Review Stop E
Sequence Number 2
Notes
Date Text
2018-09-22 13:38:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. LOAD CALCULATION PROVIDED HAS SOME ITEMS NOT
 INCLUDED AND DEMAND FACTOR APPLIED INCORRECTLY. SEE
 FORMAT IN FBC RESIDENTIAL. NEC 220; FBC RE E3602.2
 (LOAD CALCULATION NOT CORRECT. A LAUNDRY CIRCUIT MUST
 BE INCLUDED AT 1500 VA, AND THIS IS SEPARATE FROM THE
 DRYER WHICH MUST BE CALCULATED AT A MINIMUM OF 5000 VA,
 BREAKER SHOWN FOR DRYER IS 50 AMP WHICH IS MUCH MORE
 THAN 4500 VA. NEC 220.52 AND 220.54)
 2. PROVIDE ACCURATE PANEL SCHEDULE INDICATING ALL
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. WATER HEATER IS NOT SHOWN. NEC 210.8,
 210.12, 210.19, 210.20, 215.5, 408.4; WPB FBC 107.3.5;
 FBC RE E3706.2, E3902 (WATER HEATER NOT SHOWN IN PANEL
 SCHEDULE, AFCI PROTECTION NOT SHOWN CORRECTLY.)
 3. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902.16 (NOT CORRECTED, NOTE
 STATES THAT RECEPTACLES SHALL BE AFCI PROTECTED WHICH
 IS NOT CODE COMPLIANT.)
 4. CORRECTED.
 5. CORRECTED.
 6. TRANSFER SWITCH REMOVED.
 7. CORRECTED.
 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3 (NOT PROVIDED)
 9. CORRECTED.
 10. PROVIDE ACCURATE RISER DIAGRAM. THE EQUIPMENT
 GROUNDING CONDUCTOR (EGC) SHOULD NOT BE INCLUDED IN THE
 CONDUIT FROM THE METER TO THE MANUAL TRANSFER SWITCH.
 THE EGC FROM THE MANUAL TRANSFER SWITCH TO THE INTERIOR
 PANEL IS NOT SIZED PROPERLY. INTERIOR PANEL STATES THAT
 IS HAS A 125 AMP MAIN, AND BELOW THAT STATES THAT IT
 HAS A 150 AMP MAIN. CORRECT DISCREPANCY. NEC 215.5,
 250.6, 250.122; WPB FBC 107.2.1; FBC RE E3704.6,
 3607.3.1 (RISER STILL NOT CORRECT. RISER DIAGRAM SHOWS
 A FEED FROM THE METER TO THE INTERIOR PANEL WHICH IS
 LOCATED IN THE DINING ROOM. CONDUCTORS THAT ARE NOT
 PROTECTED BY A MAIN BREAKER OR DISCONNECT ARE NOT
 PERMITTED TO RUN THROUGH THE HOUSE IN THIS FASHION.
 PROVIDE EITHER A MAIN ON THE OUTSIDE OF THE HOME, OR
 INSTALL THE CONDUCTORS UNDER THE SLAB. IF CONDUCTORS
 ARE INSTALLED UNDER THE SLAB, THEN THERE SHOULD NOT BE
 AN EQUIPMENT GROUNDING CONDUCTOR IN THIS CONDUIT. IF
 THERE IS A MAIN BREAKER, THAN THE EGC IS NOT SIZED
 PROPERLY. PROVIDE CORRECTIONS. NEC 230.70, 250.6; FBC
 RE E3601.6)
 11. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 (NOT
 SHOWN ON RISER DIAGRAM)
 12. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4 (NOT CORRECTED, ALSO
 SIZE OF GROUNDING ELECTRODE CONDUCTOR IS NOT CODE
 COMPLIANT. PROVIDE CORRECTION. NEC 250.66)
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
  
 NEW COMMENT:
  
 16. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy