2018-10-29 09:01:13PLUMBING PROVISO:
 1. SHOW MOP SINK FOR THE GROUND FLOOR P-4 ON THE
 SANITARY ISOMETRIC SHT. P-3.03. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
 1. PROVIDE RISER DIAGRAM FOR THE CONDENSATE AND WATER
 HEATER DRAIN PAN. . PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER