| 2018-10-26 16:58:08 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18061140 |
| | 9/27/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THIS IS THE 3RD REQUEST TO CHANGE THE AC HEAT LOAD |
| | CALCULATION LOCATION TO WEST PALM BEACH FROM MIAMI. |
| | |
| | 2) M-204: THE USE OF THE CORRIDOR SUPPLY AIR AS MAKEUP |
| | AIR FOR THE DRYER EXHAUST IS NOT IN COMPLIANCE WITH |
| | SECTION 601.2 (1), BECAUSE THERE IS INADEQUATE AIR IN |
| | THE CORRIDOR TO SUPPLY THE LAUNDRY ROOM AND STILL |
| | REMAIN POSITIVELY PRESSURIZED- SEE BELOW. |
| | |
| | 601.2 AIR MOVEMENT IN EGRESS ELEMENTS. |
| | CORRIDORS SHALL NOT SERVE AS SUPPLY, RETURN, EXHAUST, |
| | RELIEF OR VENTILATION AIR DUCTS. |
| | |
| | EXCEPTIONS: |
| | 1.USE OF A CORRIDOR AS A SOURCE OF MAKEUP AIR FOR |
| | EXHAUST SYSTEMS IN ROOMS THAT OPEN DIRECTLY ONTO SUCH |
| | CORRIDORS, INCLUDING TOILET ROOMS, BATHROOMS, DRESSING |
| | ROOMS, SMOKING LOUNGES AND JANITOR CLOSETS, SHALL BE |
| | PERMITTED, PROVIDED THAT EACH SUCH CORRIDOR IS DIRECTLY |
| | SUPPLIED WITH OUTDOOR AIR AT A RATE GREATER THAN THE |
| | RATE OF MAKEUP AIR TAKEN FROM THE CORRIDOR. |
| | |
| | 7) UPDATAD DEFERRED SUBMITTAL LIST: |
| | |
| | A) GENERATOR |
| | B) DRYERS |
| | C) FIRE DAMPERS |
| | D) MOTORIZED OUTSIDE AIR DAMPERS |
| | E) DUCT SMOKE DETECTORS |
| | F) OUTSIDE AIR AND EXHAUST INLET LOUVERS, INCLUDING |
| | PRODUCT DATA SHEETS AND NOA'S. |
| | G) AC CONDENSER STAND NOA |
| | H) KITCHEN EXHAUST HOODS |
| | I) AC REFRIGERANT RISER |
| | K) DRYER BOOSTER FAN |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |