Date Text
2018-10-03 07:59:472ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 NOT COMPLIED 8. SHT. P- 3.00 PLEASE ENLARGE THE WATER
 AND SANITARY ISOMETRIC DRAWING ON SEPARATE SHEETS THEY
 ARE TO CONGESTED TO DETERMINE CODE COMPLIANCE. PER WPB
 AMEND TO FBC 107.3.5.1.3(13) SHT. P-3.0 WAS NOT REVISED
 AND THE SANITARY ISOMETRIC THAT WAS ADDED TO SHT.
 P.3.03 IS MORE CONGESTED AND OVERLAPS THE SOIL STACK
 RISER. THE SANITARY NEEDS TO BE ENLARGED AND PLACED ON
 SEPARATE SHEET.
  
 COMPLIED PARTIALLY 9. SHT. P- 3.00 SHOW THE PIPE SIZE
 ON THE WATER AND SANITARY ISOMETRIC DRAWINGS. PER WPB
 AMEND TO FBC 107.3.5.1.3(13) NEED TO SIZE ALL THE
 BRANCHES ON THE WATER ISOMETRIC.
  
 COMPLIED PARTIALLY 10. P -4.01 THE ELECTRIC WATER
 HEATER DETAIL HAS THE FOLLOWING CODE VIOLATIONS.
 C) SHOWS WATER HEATER MOUNTED ON SHELF IS THIS CORRECT
 AN 80 GAL HEATER ON THE SHELF IF SO PROVIDE DETAIL FOR
 SHELVING TO HOLD THE WEIGHT OF THE 80 GAL HEATER 800LBS
 + PER WPB AMEND TO FBC 107.2.1 PROVIDE A DETAIL FOR THE
 SHELVING FOR THE 80 GAL HEATER IT SHALL BA ABLE TO
 SUPPORT 1000 POUNDS OR MORE.
  
 COMPLIED PARTIALLY 11. A SERVICE SINK IS REQUIRED ON
 GROUND FLOOR PE FBC PL TABLE 403.1 MOP SINK NOT ADDED
 TO ISOMETRIC DRAWING PLEASE CLARIFY.
  
 NEW COMMENTS:
  
 1. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND SIZING
 FOR THE LINT INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 2. THE DISCHARGE FROM THE ELEVATOR SUMP PUMP SHALL
 DISCHARGE INTO OIL SEPARATOR OR HAVE AN OILMINDER ALARM
 ON THE PUMP PROVIDE MANUFACTURE SPECIFICATIONS ON PUMP
 AND OIL SEPARATOR IF ONE IS BEING USED. PER FBC PL
 1003.4
  
 3. PLEASE PROVIDE ISOMETRIC FOR CONDENSATE AND WATER
 HEATER PAN DRAIN. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  