| 2018-10-03 07:59:47 | 2ND REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED |
| | |
| | NOT COMPLIED 8. SHT. P- 3.00 PLEASE ENLARGE THE WATER |
| | AND SANITARY ISOMETRIC DRAWING ON SEPARATE SHEETS THEY |
| | ARE TO CONGESTED TO DETERMINE CODE COMPLIANCE. PER WPB |
| | AMEND TO FBC 107.3.5.1.3(13) SHT. P-3.0 WAS NOT REVISED |
| | AND THE SANITARY ISOMETRIC THAT WAS ADDED TO SHT. |
| | P.3.03 IS MORE CONGESTED AND OVERLAPS THE SOIL STACK |
| | RISER. THE SANITARY NEEDS TO BE ENLARGED AND PLACED ON |
| | SEPARATE SHEET. |
| | |
| | COMPLIED PARTIALLY 9. SHT. P- 3.00 SHOW THE PIPE SIZE |
| | ON THE WATER AND SANITARY ISOMETRIC DRAWINGS. PER WPB |
| | AMEND TO FBC 107.3.5.1.3(13) NEED TO SIZE ALL THE |
| | BRANCHES ON THE WATER ISOMETRIC. |
| | |
| | COMPLIED PARTIALLY 10. P -4.01 THE ELECTRIC WATER |
| | HEATER DETAIL HAS THE FOLLOWING CODE VIOLATIONS. |
| | C) SHOWS WATER HEATER MOUNTED ON SHELF IS THIS CORRECT |
| | AN 80 GAL HEATER ON THE SHELF IF SO PROVIDE DETAIL FOR |
| | SHELVING TO HOLD THE WEIGHT OF THE 80 GAL HEATER 800LBS |
| | + PER WPB AMEND TO FBC 107.2.1 PROVIDE A DETAIL FOR THE |
| | SHELVING FOR THE 80 GAL HEATER IT SHALL BA ABLE TO |
| | SUPPORT 1000 POUNDS OR MORE. |
| | |
| | COMPLIED PARTIALLY 11. A SERVICE SINK IS REQUIRED ON |
| | GROUND FLOOR PE FBC PL TABLE 403.1 MOP SINK NOT ADDED |
| | TO ISOMETRIC DRAWING PLEASE CLARIFY. |
| | |
| | NEW COMMENTS: |
| | |
| | 1. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND SIZING |
| | FOR THE LINT INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. THE DISCHARGE FROM THE ELEVATOR SUMP PUMP SHALL |
| | DISCHARGE INTO OIL SEPARATOR OR HAVE AN OILMINDER ALARM |
| | ON THE PUMP PROVIDE MANUFACTURE SPECIFICATIONS ON PUMP |
| | AND OIL SEPARATOR IF ONE IS BEING USED. PER FBC PL |
| | 1003.4 |
| | |
| | 3. PLEASE PROVIDE ISOMETRIC FOR CONDENSATE AND WATER |
| | HEATER PAN DRAIN. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |