| 2018-09-27 14:59:05 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18061140 |
| | 9/27/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE CORRECTED HEAT LOAD CALCULATIONS WERE NOT |
| | SUBMITTED- SEE 1ST REVIEW COMMENT #2- SECTION C402.3.1 |
| | FBC EC. |
| | |
| | 2) SHEET M-101: PLEASE PROVIDE AN EXHAUST VENTILATION |
| | CALCULATION FOR THE PARKING GARAGE AREA, AND INDICATE |
| | THE SEQUENCE OF OPERATION FOR THE FANS- SECTION 404.1 |
| | AND 502.13 FBC M. |
| | |
| | 3) M-204: THERE IS NO LEGEND TO CLARIFY WHAT THE "FS" |
| | LABEL AND THE"F" DEVICE SYMBOL PLACED AT THE DRYER |
| | EXHAUST DUCT/WALL PENETRATIONS STAND FOR- SECTION 107.1 |
| | WPB. |
| | |
| | 4) M-204: THE REQUESTED MAKE UP AIR FOR THE DRYERS AND |
| | AIR BALANCE CALCULATIONS FOR THE LAUNDRY ROOM NOT |
| | PROVIDED- SECTION 504.6 FBC M. |
| | |
| | 5) M-101: THE REQUESTED DUCT SMOKE DETECTORS IN THE |
| | SUPPLY SYSTEM NOT PROVIDED FOR THE 5-TON SYSTEMS- SEE |
| | 1ST REVIEW COMMENT #12 AND SECTION 606.2.1 FBC M. |
| | |
| | 6) AS PREVIOUSLY REQUESTED PROVIDE A CONDENSATE PIPING |
| | RISER AND FLOOR PLAN DRAWING- SEE 1ST REVIEW COMMENT |
| | #16 |
| | |
| | 7) UPDATAD DEFERRED SUBMITTAL LIST: |
| | |
| | A) GENERATOR |
| | B) DRYERS |
| | C) FIRE DAMPERS |
| | D) MOTORIZED OUTSIDE AIR DAMPERS |
| | E) DUCT SMOKE DETECTORS |
| | F) OUTSIDE AIR AND EXHAUST INLET LOUVERS, INCLUDING |
| | PRODUCT DATA SHEETS AND NOA'S. |
| | G) AC CONDENSER STAND NOA |
| | H) KITCHEN EXHAUST HOODS |
| | I) AC REFRIGERANT RISER |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |