| 2018-10-15 07:47:51 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18061140 |
| | REVIEWED: AUGUST 17, 2018 |
| | 2ND REVIEW OCTOBER 15, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1-7. OK |
| | |
| | 8. [FBC AMENDED 107.3.5] |
| | -STAIR 2 4 TH FLOOR LANDING SHOULD HAVE GUARD RAIL AND |
| | NOT APPEAR TO CONTINUE GOING UP SINCE IT IS THE FINAL |
| | LANDING. |
| | 8-2 NOT FULLY ADDRESSED. LOOK AT 4TH FLOOR LANDING ON |
| | SHEET A-1.04, IT SHOULD MATCH SHEET A-5.02 FOR 4TH |
| | FLOOR LANDING. |
| | |
| | 9-38. OK |
| | |
| | NEW COMMENT: |
| | [FBC AMENDED 110.8.4.4]ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY |
| | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND CHAPTER 633 FLORIDA |
| | STATUTES. |
| | |
| | PLEASE PROVIDE ONE ARCHITECTURAL SHEET AND ONE |
| | STRUCTURAL SHEET WITH THE PHRASE FROM [FBC AMENDED |
| | 110.8.4.4] |
| | INDEX SHEET OR GENERAL NOTES SHEET WOULD WORK. |
| | |
| | THIS REQUIREMENT IS PART OF THRESHOLD BUILDING. SEE |
| | THRESHOLD COMMENTS FOR ADDITIONAL THRESHOLD |
| | REQUIREMENTS. |
| | |
| | PROVISO: DERFERED SUBMITTALS |
| | ROOFING |
| | GUARDS AND HANDRAILS |
| | TRASH CHUTE |
| | FENESTRATION |
| | FLOORING SUBMITTAL WITH REPORTS FOR ICC, STC AND FLAME |
| | SPREAD/SMOKE DEVELOPED INDEX. |
| | SHORING/RE-SHORING |
| | |
| | |