2018-08-13 11:05:281ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE INDICATE ON THE ENLARGED UNIT PLANS WHAT THE
 DESIGN SPEC THE BATHROOM IS A OR B PER FHA GUIDELINES.
  
 2. PLEASE SHOW CLEAR FLOOR SPACE FOR WATER CLOSETS ON
 THE ENLARGED UNITS PLANS PER FHA G REQ. 7 (2)(A)(III)
 OR (B)(IV)
  
 3. SHT. G-007 UNDER THE REQUIREMENT IT IS REFERENCING A
 DETAIL ON SHT. A-3.1.2 I WAS UNABLE TO LOCATE THIS PAGE
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE PROVIDE A DETAIL SHOWING THE DIMENSIONS OF
 THE EMERGENCY SCUPPER. PER WPB AMEND TO FBC 107.2.1
  
 5. THE BREAKROOM SINK AND THE SINK IN THE COMMUNITY
 ROOM SHALL BE MOUNTED WITH THE COUNTER OR RIM NO HIGHER
 THAN 34" AND A CLEAR FLOOR SPACE OF 30" X 48" PER FHAG
 REQ. #2(14) / (ANSI) A117.1-1986 4.19.2.2, 4.19.3
  
 6. SEPARATE PERMITS ARE REQUIRED FOR BACKFLOW
 ASSEMBLIES LOCATED AT METER PLEASE PLACE NOTE ON PLAN.
 PER WPB AMEND TO FBC 107.2.1
  
 7. PROVIDE DETAIL WITH THE DIMENSION FOR THE
 ACCESSIBILITY IN THE COMMON BATHROOMS OM THE GROUND
 FLOOR. PER FHAG REQ. #2(14) / (ANSI) A117.1-1986
 A) CLEAR FLOOR SPACE FOR TOILET. 416.2 , 417.3
 B) GRAB BARS 4.17.6
 C) LAVATORY 4.19.2
  
 8. SHT. P- 3.00 PLEASE ENLARGE THE WATER AND SANITARY
 ISOMETRIC DRAWING ON SEPARATE SHEETS THEY ARE TO
 CONGESTED TO DETERMINE CODE COMPLIANCE. PER WPB AMEND
 TO FBC 107.3.5.1.3(13)
  
 9. SHT. P- 3.00 SHOW THE PIPE SIZE ON THE WATER AND
 SANITARY ISOMETRIC DRAWINGS. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 10. P -4.01 THE ELECTRIC WATER HEATER DETAIL HAS THE
 FOLLOWING CODE VIOLATIONS.
 A) IT SHOWS THE T + P RELIEF PIPING DISCHARGING INTO A
 MOP SINK THERE IS NO MOP SINK SHOW THE PIPIG SHALL
 COMPLY WITH FBC PL 504.6. 2.DISCHARGE THROUGH AN AIR
 GAP LOCATED IN THE SAME ROOM AS THE WATER HEATER.
 B)IT SHOWS DRAIN PAN DISCHARGING TO MOP SINK NO MOP
 SINK SHOWN PLEASE CLARIFY
 C) SHOWS WATER HEATER MOUNTED ON SHELF IS THIS CORRECT
 AN 80 GAL HEATER ON THE SHELF IF SO PROVIDE DETAIL FOR
 SHELVING TO HOLD THE WEIGHT OF THE 80 GAL HEATER 800LBS
 + PER WPB AMEND TO FBC 107.2.1
  
 11. A SERVICE SINK IS REQUIRED ON GROUND FLOOR PE FBC
 PL TABLE 403.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH