2018-07-20 15:18:361ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18061140
 7/20/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT AN ENERGY COMPLIANCE REPORT IN ACCORDANCE
 WITH SECTIONS C101.5 AND C401.2 FBC EC.
  
 2) THE HEAT LOAD CALCULATIONS ARE INDICATING MIAMI AS
 THE LOCATION USED TO ESTABLISH DRY AND WET BULB
 TEMPERATURES- PLEASE CORRECT.
  
 3) SHEET M-101: THE PARKING AREA ON THE NORTH SIDE OF
 THE BUILDING IS CLASSIFIED AS AN ENCLOSED PARKING
 GARAGE PER SECTIONS 406.5.1, 406.5.2, AND 406.6 FBC B.
 PROVIDE A MECHANICAL VENTILATION SYSTEM AS REQUIRED BY
 SECTION 406.6.2 FBC B, AND IN COMPLIANCE WITH SECTION
 404 FBC M.
  
 4) M-101: THE DRYER, TOILET, AND FIRE PUMP EXHAUST
 SYSTEMS SHALL NOT TERMINATE AND DISCHARGE INTO THE
 ENCLOSED PARKING GARAGE PER SECTION 501.3 FBC M. PLEASE
 RELOCATE THESE TERRMINATIONS TO LOCATIONS IN
 COMPLIANCE.
  
 5) M-101 & M-501: A SECTION CUT OF THE GENERATOR AND
 GENERATOR ROOM IS SHOWN ON SHEET M-501. HOWEVER THERE
 IS NO GENERATOR OR GENERATOR ROOM SHOWN ON THE PLAN.
  
 6) M-201, 202, & 203: A) PLEASE UPDATE NOTE #4 TO THE
 CURRENT FBC-17 MECHANICAL CODE. B) IN REFERENCE TO NOTE
 #2B, THE WEST PALM BEACH BUILDING DEPARTMENT DOES NOT
 PERFORM INSPECTIONS ON INTUMESCENT PAINT APPLICATIONS,
 AND WILL REQUIRE THE DESIGN PROFESSIONAL OF RECORD TO
 CERTIFY THE APPLICATIONS. C) REMOVE NOTE #13 AS NO
 OUTSIDE AIR DUCTS ARE SHOWN ON THE PLANS AND
  
 SHEET M-300 SPECIFIES NATURAL VENTILATION.
  
 7) M-204: WHICH AC SYSTEM IS BEING INSTALLED IN THE AC
 CLOSET 112.1.
  
 8) M-204: SUPPLY DUCT FOR RESTROOM 113 NOT SHOWN.
  
 9) M-204: INDICATE HOW MAKEUP AIR IS BEING PROVIDED FOR
 THE LAUNDRY ROOM AND PROVIDE AN AIR BALANCE CALCULATION
  
 10 )M-204: OUTSIDE AIR DUCT AND DAMPER FOR FCU-B NOT
 SHOWN.
  
 11) M-300: PLEASE INCLUDE THE CORRIDORS ON THE 2ND,
 3RD, AND 4TH FLOORS IN THE O/A CALCS.
  
 12) M-300: THE HVAC DESIGN TABLE INDICATES DUCT SMOKE
 DETECTORS HOWEVER NONE ARE SHOWN ON THE PLANS- PLEASE
 CORRECT AND NOTE THAT SYSTEMS FCU-D, E, & F ARE 5-TON
 SYSTEMS WHICH TYPICALLY HAVE THE CAPACITIES TO EXCEED
 2000 CFMS OF SUPPLY AIR. PLEASE PROVIDE A DUCT SMOKE
 DETECTOR IN THE SUPPLY SYSTEMS OF THE AIR HANDLERS-
 SECTION 606.2.1 FBC M.
  
 13) M-400: PLEASE INDICATE THE REFRIGERANT PIPING
 SIZES, AND SHOW THE PIPING RUNS ON THE FLOOR PLANS.
  
 14) M-501: THE MIAMI-DADE NOA #15-0902.02 HAS BEEN
 SUPERSEDED BY #17-1218.02. PLEASE CORRECT THE NOTE AND
 SUBMIT TWO COPIES OF THE NOA.
  
 15) PROVIDE A CONDENSATE PIPING RISER, AND SHOW THE
 PIPING RUNS ON THE PLUMBING FLOOR PLANS.
  
 16) REQUIRED PRODUCT SUBMITTALS:
  
 A) GENERATOR
 B) DRYERS
 C) FIRE DAMPERS
 D) MOTORIZED OUTSIDE AIR DAMPERS
 E) DUCT SMOKE DETECTORS
 F) OUTSIDE AIR AND EXHAUST INLET LOUVERS, INCLUDING
 PRODUCT DATA SHEETS AND NOA'S.
 G) AC CONDENSER STAND NOA
 H) KITCHEN EXHAUST HOODS
  
 17) ADVISORY: A TEST AND BALANCE REPORT FOR THE AC
 SYSTEMS WILL BE REQUIRED AT FINAL MECHANICAL
 INSPECTION- SECTION 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  