| 2018-07-20 15:18:36 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18061140 |
| | 7/20/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SUBMIT AN ENERGY COMPLIANCE REPORT IN ACCORDANCE |
| | WITH SECTIONS C101.5 AND C401.2 FBC EC. |
| | |
| | 2) THE HEAT LOAD CALCULATIONS ARE INDICATING MIAMI AS |
| | THE LOCATION USED TO ESTABLISH DRY AND WET BULB |
| | TEMPERATURES- PLEASE CORRECT. |
| | |
| | 3) SHEET M-101: THE PARKING AREA ON THE NORTH SIDE OF |
| | THE BUILDING IS CLASSIFIED AS AN ENCLOSED PARKING |
| | GARAGE PER SECTIONS 406.5.1, 406.5.2, AND 406.6 FBC B. |
| | PROVIDE A MECHANICAL VENTILATION SYSTEM AS REQUIRED BY |
| | SECTION 406.6.2 FBC B, AND IN COMPLIANCE WITH SECTION |
| | 404 FBC M. |
| | |
| | 4) M-101: THE DRYER, TOILET, AND FIRE PUMP EXHAUST |
| | SYSTEMS SHALL NOT TERMINATE AND DISCHARGE INTO THE |
| | ENCLOSED PARKING GARAGE PER SECTION 501.3 FBC M. PLEASE |
| | RELOCATE THESE TERRMINATIONS TO LOCATIONS IN |
| | COMPLIANCE. |
| | |
| | 5) M-101 & M-501: A SECTION CUT OF THE GENERATOR AND |
| | GENERATOR ROOM IS SHOWN ON SHEET M-501. HOWEVER THERE |
| | IS NO GENERATOR OR GENERATOR ROOM SHOWN ON THE PLAN. |
| | |
| | 6) M-201, 202, & 203: A) PLEASE UPDATE NOTE #4 TO THE |
| | CURRENT FBC-17 MECHANICAL CODE. B) IN REFERENCE TO NOTE |
| | #2B, THE WEST PALM BEACH BUILDING DEPARTMENT DOES NOT |
| | PERFORM INSPECTIONS ON INTUMESCENT PAINT APPLICATIONS, |
| | AND WILL REQUIRE THE DESIGN PROFESSIONAL OF RECORD TO |
| | CERTIFY THE APPLICATIONS. C) REMOVE NOTE #13 AS NO |
| | OUTSIDE AIR DUCTS ARE SHOWN ON THE PLANS AND |
| | |
| | SHEET M-300 SPECIFIES NATURAL VENTILATION. |
| | |
| | 7) M-204: WHICH AC SYSTEM IS BEING INSTALLED IN THE AC |
| | CLOSET 112.1. |
| | |
| | 8) M-204: SUPPLY DUCT FOR RESTROOM 113 NOT SHOWN. |
| | |
| | 9) M-204: INDICATE HOW MAKEUP AIR IS BEING PROVIDED FOR |
| | THE LAUNDRY ROOM AND PROVIDE AN AIR BALANCE CALCULATION |
| | |
| | 10 )M-204: OUTSIDE AIR DUCT AND DAMPER FOR FCU-B NOT |
| | SHOWN. |
| | |
| | 11) M-300: PLEASE INCLUDE THE CORRIDORS ON THE 2ND, |
| | 3RD, AND 4TH FLOORS IN THE O/A CALCS. |
| | |
| | 12) M-300: THE HVAC DESIGN TABLE INDICATES DUCT SMOKE |
| | DETECTORS HOWEVER NONE ARE SHOWN ON THE PLANS- PLEASE |
| | CORRECT AND NOTE THAT SYSTEMS FCU-D, E, & F ARE 5-TON |
| | SYSTEMS WHICH TYPICALLY HAVE THE CAPACITIES TO EXCEED |
| | 2000 CFMS OF SUPPLY AIR. PLEASE PROVIDE A DUCT SMOKE |
| | DETECTOR IN THE SUPPLY SYSTEMS OF THE AIR HANDLERS- |
| | SECTION 606.2.1 FBC M. |
| | |
| | 13) M-400: PLEASE INDICATE THE REFRIGERANT PIPING |
| | SIZES, AND SHOW THE PIPING RUNS ON THE FLOOR PLANS. |
| | |
| | 14) M-501: THE MIAMI-DADE NOA #15-0902.02 HAS BEEN |
| | SUPERSEDED BY #17-1218.02. PLEASE CORRECT THE NOTE AND |
| | SUBMIT TWO COPIES OF THE NOA. |
| | |
| | 15) PROVIDE A CONDENSATE PIPING RISER, AND SHOW THE |
| | PIPING RUNS ON THE PLUMBING FLOOR PLANS. |
| | |
| | 16) REQUIRED PRODUCT SUBMITTALS: |
| | |
| | A) GENERATOR |
| | B) DRYERS |
| | C) FIRE DAMPERS |
| | D) MOTORIZED OUTSIDE AIR DAMPERS |
| | E) DUCT SMOKE DETECTORS |
| | F) OUTSIDE AIR AND EXHAUST INLET LOUVERS, INCLUDING |
| | PRODUCT DATA SHEETS AND NOA'S. |
| | G) AC CONDENSER STAND NOA |
| | H) KITCHEN EXHAUST HOODS |
| | |
| | 17) ADVISORY: A TEST AND BALANCE REPORT FOR THE AC |
| | SYSTEMS WILL BE REQUIRED AT FINAL MECHANICAL |
| | INSPECTION- SECTION 107.2.1 WPB. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |