2018-07-25 12:21:59FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 LOAD CALCULATION REQUIRED TO BE DONE IN ACCORDANCE WITH
 ARTICLE 220
  
 FAULT CURRENT CALCULATION REQUIRED PER 110.24
  
 MAIN SERVICE OCP OF1200 AMPERES SHALL MEET THE
 REQIREMENTS OF 240.87
  
 PAGE E-1.01
  
 AC ROOMS 109. 119.1, 102.1, 118.2 MISSING SERVICE
 OUTLET FOR THE AC.
  
 PAGE E-1.02
  
 X-15 CLOSETS NEED SERVIE OUTLET FOR THE AC
  
 PAGE E-2.01
  
 PANEL SCHEDULE SHOWS GFI ON SOME CIRCUIT BUT NOT ALL
 REQUIRED CIRCUITS, AFCI PROTECTION IS ALSO MISSING.
 210.8, 210.12(A)(B)
  
 PAGE E-3.01
  
 NEED TO SHOW SIZE OF CONTROLER FOR FIRE PUMP
  
 PAGE E-3.02
  
 FIRE ALARM SYSTEM, PROVIDE SEPARATE PLANS AND PERMIT
 FOR THIS SYSTEM.
  
 PAGE E-3.03
  
 LOW VOLTAGE SYSTEMS REQUIRE A SEPARATE PERMIT.
  
 PAGE E-3.04
  
 FIRE FIGHTER COMMUNICATION SYSTEM REQUIRES SEPARATE
 PLANS AND PERMITS FOR THIS SYSTEM
  
 PAGE E-4.04
  
 LAUNDRY AREA RECEPTACLES REQUIRE AFCI AND GFCI
 PROTECTION 210.8, 210.12(A)(B)
  
 PAGE E-5.01, E-5.02, E-5.03
 AFCI AND GFCI PROTECTION TO BE DONE IN ACCORDANCE WITH
 210.8, AND 210,12(A)(B)
  
  