| Plan Review Notes For Permit 18061140 |
| Permit Number |
18061140 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-07-25 12:21:59 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | LOAD CALCULATION REQUIRED TO BE DONE IN ACCORDANCE WITH | | | ARTICLE 220 | | | | | | FAULT CURRENT CALCULATION REQUIRED PER 110.24 | | | | | | MAIN SERVICE OCP OF1200 AMPERES SHALL MEET THE | | | REQIREMENTS OF 240.87 | | | | | | PAGE E-1.01 | | | | | | AC ROOMS 109. 119.1, 102.1, 118.2 MISSING SERVICE | | | OUTLET FOR THE AC. | | | | | | PAGE E-1.02 | | | | | | X-15 CLOSETS NEED SERVIE OUTLET FOR THE AC | | | | | | PAGE E-2.01 | | | | | | PANEL SCHEDULE SHOWS GFI ON SOME CIRCUIT BUT NOT ALL | | | REQUIRED CIRCUITS, AFCI PROTECTION IS ALSO MISSING. | | | 210.8, 210.12(A)(B) | | | | | | PAGE E-3.01 | | | | | | NEED TO SHOW SIZE OF CONTROLER FOR FIRE PUMP | | | | | | PAGE E-3.02 | | | | | | FIRE ALARM SYSTEM, PROVIDE SEPARATE PLANS AND PERMIT | | | FOR THIS SYSTEM. | | | | | | PAGE E-3.03 | | | | | | LOW VOLTAGE SYSTEMS REQUIRE A SEPARATE PERMIT. | | | | | | PAGE E-3.04 | | | | | | FIRE FIGHTER COMMUNICATION SYSTEM REQUIRES SEPARATE | | | PLANS AND PERMITS FOR THIS SYSTEM | | | | | | PAGE E-4.04 | | | | | | LAUNDRY AREA RECEPTACLES REQUIRE AFCI AND GFCI | | | PROTECTION 210.8, 210.12(A)(B) | | | | | | PAGE E-5.01, E-5.02, E-5.03 | | | AFCI AND GFCI PROTECTION TO BE DONE IN ACCORDANCE WITH | | | 210.8, AND 210,12(A)(B) | | | | | | |
|