2018-08-20 09:01:59****CORRECTIONS****
 W.P.B. PERMIT: 18061140
 REVIEWED: AUGUST 17, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEPARATE PERMIT REQUIRED FOR DEMO,
 ENGINEERING(CIVIL), LANDSCAPING, IRRIGATION, FENCING,
 DUMPSTER ENCLOSURE AND GENERATOR.
  
 2. [FBC AMENDED 107.2.5]THE SUREVEY PROVIDED SHOWS
 EXISTING CONDITIONS, WHICH IS GOOD FOR THE DEMO PERMIT.
 PLEASE PROVIDE SURVEY TO SHOW NEW BUILDING ON THE SITE.
 SHOW LOWEST FOOR ELEVATION, AND PROVIDE ELEVATIONS IN
 NAVD88.
  
 3. [FBC AMENDED 107.3.5]PLEASE UPDATE INDEX SHEET TO
 INCLUDE G-0.09. I WILL BE PUTTING APPROVAL STAMP ON
 THAT PAGE TO INDICATE ALL SHEETS REVIEWED.
  
 4. SHEETS A-7.02 THRU A-7.09 NAME DESCRIPTION DOESN?T
 MATCH THE SHEET PROVIDED. EX: SHEET A7.02 SAYS WINDOW
 SCHEDULE ON INDEX SHEET, BUT IT IS ACTUALLY GLAZING
 DETAIL SHEET.
  
 5. SHEET A-0.03 SHOW IN INDEX BUT NOT UPLOADED. PLEASE
 UPLOAD SHEET A-0.03 ACCESSIBILITY PLAN.
  
 6. SHEET A-5.02 IS NOT UP-LOAD AND IT IS NEEDED FOR
 STAIR 2 DETAILS.
  
 7. [FBC AMENDED 107.3.5]UPDATE INDEX SECTION FOR
 STRUCTURAL. IT SHOWS AS 8 STORY BUILDING AND SHEETS
 DON?T MATCH WHAT WAS UPLOADED.
 ALSO, SHEETS ARE MISSING. I CAN?T DO A FULL REVIEW
 UNTIL ALL STRUCTURAL SHEETS ARE PROVIDED.
 PLEASE REVIEW STRUCTURAL SECTION IN PROJECT DOX TO
 COMPARE TO ADJUSTED INDEX.
  
 8. [FBC AMENDED 107.3.5]PLEASE UPDATE ALL DRAINGS
 INCLUDING LIFE SAFETY, FLOOR PLANS AND ROOF ACCESS TO
 SHOW HOW STAIRS WORK. LOOKING MAINLY AT AT THE FIRST
 FLOOR, 4 TH FLOOR(STAIR #2) ROOF LANDING(STAIR #1).
 SOME OF THE THINGS I SEE INCLUDE, BUT ARE NOT LIMITED
 TO:
 -STAIR 1 AT GROUND FLOOR SHOULD EXTEND INTO CORRIDOR
 SINCE THAT DISTANCE BETWEEN FLOORS IS GREATER THAN THE
 UPPER FLOORS.
 -STAIR 1 ROOF LANDING SHOULD HAVE GUARD RAIL AND NOT
 APPEAR TO CONTINUE GOING UP SINCE IT IS THE FINAL
 LANDING. IT ALSO EXITS ONTO ROOF DIFFERNTLY BETWEEN
 PLANS AND DETAILS.
 -STAIR 2 4 TH FLOOR LANDING SHOULD HAVE GUARD RAIL AND
 NOT APPEAR TO CONTINUE GOING UP SINCE IT IS THE FINAL
 LANDING.
  
 9. PLEASE REVIEW ALL STAIRS AND SUPPLY MISSING SHEET
 A-5.02.
 ALSO, IF POSSIBLE ON SHEET A5.01 AND A5.02 CAN YOU KEEP
 THE SAME ORIENTAION AS THE PLANS FOR ENLARGED DETAILS.
  
 10. UPDATE ALL LIFE SAFETY SHEETS FOR THE CURRENT CODE
 VERSION FBC 2017 6TH EDITION. I SEE THREE INSTANCES
 TOTAL(GENERAL NOTES, TRAVEL AND VERTICAL ORIENTED IN
 OCCUPANCY USE)ON ALL FOUR SHEETS.
  
 11. SHEET A-S.03 STAIR SIGNAGE JPG. DIDN?T ATTACH TO
 DRAWING. ADD STAIR SIGNAGE DETAIL.
  
 12. SHEET A-7.05 IMPACT INSULATION AND SOUND
 TRANSMISSION CLASS ARE FOR 6? SLAB. THE FLOORS IN THIS
 PROJECT ARE TO BE 8?.
  
 13. SHEET A7.03 DOOR SCHEDULE REFERS TO ?SEE INTERIOR
 GLAZING?. I SEE REFERENCE TO TEMPERED GLASS, BUT WHAT
 ABOUT FIRE RATING ON DOORS IN THE CORRIDOR(2 HR RATED
 FIRE CORRIDOR).ALSO, THE NOTES BELOW INTERIOR GLAZING
 ARE FOR EXTERIOR DOORS.
  
 14. [FBC ACCESSIBILITY 402.1]PROVIDE ACCESSIBLE ROUTE
 FROM PARKING LOT.
  
 15. [FBC ACCESSIBILITY 208.2]PROVIDE DATA USED TO
 DETERMINE AMOUNT OF ADA SPOTS.
  
 16. [FBC ACCESSIBILITY 404.2.3]DOOR ST2.1 APPEARS TO
 REDUCE THE WIDTH OF 199.1. VERIFY AND ADJUST IF
 APPLICABLE.
  
 17. [FBC ACCESSIBILITY 606.2]CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A
 FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
  
 18. [FBC ACCESSIBILITY 606.3]HEIGHT. LAVATORIES AND
 SINKS SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER
 OF THE RIM OR COUNTER SURFACE 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 THIS APPLIES TO THE 9 ADA UNITS. SHEETS A4.03(UNIT 0C),
 A4.06(UNIT 1C) AND A4.05(UNIT 1B).
  
 19. [FBC ACCESSIBILITY 804.3]KITCHEN WORK SURFACE. IN
 RESIDENTIAL DWELLING UNITS REQUIRED TO COMPLY WITH 809,
 AT LEAST ONE 30 INCHES (760 MM) WIDE MINIMUM SECTION OF
 COUNTER SHALL PROVIDE A KITCHEN WORK SURFACE THAT
 COMPLIES WITH 804.3.
  
 20. [FBC ACCESSIBILITY 804.3.2]HEIGHT. THE KITCHEN WORK
 SURFACE SHALL BE 34 INCHES (865 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.THIS APPLIES TO THE 9 ADA UNITS.
 SHEETS A4.03(UNIT 0C), A4.06(UNIT 1C) AND A4.05(UNIT
 1B).
  
 21. [FBC AMENDED 107.3.5]IS DOOR 121.2 AT GARBAGE ROOM
 A ROLL-UP DOOR? HOW DOES THE TRASH ROOM FUNCTION? FROM
 SITE PLAN AND CIVIL PLANS IT LOOKS LIKE IT EXITS ONTO
 GRASS AND A CURB.
  
 22. IF ELEVATOR PENTHOUSE GOES TO ELEVATION +50?-8? AS
 SHOWN ON A-5.04, ADJUST ELEVATIONS TO SHOW THE ELEVATOR
 PENTHOUSE AT THIS HEIGHT.
  
 23. [FBC 720.2]SHEET A-6.01 GENERAL NOTES SHOWS
 INSULATION CODE REFERENCE FOR INSULATION AS FBC 719.2.
 IT IS NOW 720.2.
  
 24. GROUND LEVEL CORRIDORS CALL FOR WALL TYPE 3. SHEET
 A-6.01 SHOW TYPE 3A TO BE 1 HOUR RATED. THIS CONFLICTS
 WITH LIFE SAFTEY PLAN WHERE IT IS ESTABLISHED AS A 2
 HOUR RATED COORIDOR. PLEASE ADJUST WALL TYPE OR DETAIL
 AS NEEDED. PROVIDE UL
  
 25. SHEET A-1.01 SHOWS THE TRASH ROOM AT 3 HOUR RATING
 AND SECTION A-5.05 SHOWS 2 HOUR WALL. THE WALL TYPE 9A
 SHOWN ON A-1.01 IS FOR 2 HOUR RATING. PLEASE
 CO-ORDINATE THE RATING TO MATCH(SAME COMMENT FOR
 STAIRS)
  
 26. SHEET A-5.05, HOW IS TRASH CHUTE FIRE STOPPING
 INSTALLED IN THIS ASSEMBLY? WILL THAT BE PART OF
 DEFFERED SUBMITTAL?
  
 27. SHEET A-5.05 SECTION 1 CALLS FOR 6 MIL AND 4? SLAB.
 STRUCTURAL, S1.01 FOUNDATION PLAN NOTES, IS CALLING FOR
 5? SLAB WITH 10 MIL. PLEASE CO-ORDINATE WITH
 STRUCTURAL.
  
 28. SHEET A3.01 CALL OUT TO A3.03 AT EXTERIOR WALLS.
 PLEASE PROVIDE THIS SHEET AS IT IS NOT PROVIDED AND
 ISN?T IN THE INDEX. ALSO, I THINK CALL OUT AT ELEVATER
 SHOULD BE 1/A-5.06 AND AT TRASH CHUTE IT SHOULD BE
 1/5.05
  
 29. SHEET A3.02 CALL OUT TO A3.03 AT EXTERIOR WALLS.
 PLEASE PROVIDE THIS SHEET AS IT IS NOT PROVIDED AND
 ISN?T IN THE INDEX.
  
 30. SHEET A-4.00 WHAT IS THE FINISH FOR ACCESSIBLE
 BALCONIES. [ANSI A137.1 ]IN FLOORING SUBMITTAL PROVIDE
 SPECIFICATION SHEET TO INCLUDE DYNAMIC COEFFICIENT OF
 FRICTION (DCOF) OF EXTERIOR FINISH BEING INSTALLED.
  
 31. [FBC AMENDED 107.3.5.1]PROVIDE STRUCTURAL ANALYSIS
 FOR STRUCTURAL LOAD BEARING COMPONANTS INCLUDING
 DEFLECTIONS OF BEAMS AND SLABS.
  
 32. [FBC 1603]SHEET S1.01 SHOWS (3)COLUMNS CC3 AT THE
 COVERE3D PARKING. WHEN I LOOK AT S1.02 I SEE 3
 ADDITIONAL COLUMNS LABELED CC7 AND BEAM 2B-2. IT
 APPEARS THAT COLUMNS CC3 CARRIES THE BEAM AND
 ADDITIONAL OFFSET COLUMNS CC7. THE END OF 2B-2 ALSO
 BEARS ON SMALLER COLUMNS CC4.
 IS THIS THE CORRECT CONFIGURATION AND DOES CC7 FOUND ON
 FL 2-4 END AT BEAM IN 2 ND FLOOR FRAMING.
  
 33. [FBC 1603]SAME COLUMNS CC3 APPEAR TO SUPPORT
 CANTILEVER APPROXIMATELY 9? FROM COLUMN TO BUILDINGS
 EDGE ABOVE FOR REMAINING OVERHANG OF PARKING AND THE
 REMAINING FLOORS. PLEASE CLARIFY THAT THIS IS CORRECT,
 OR ADJUST AS NEEDED TO TRANFER LOADS TO FOUNDATION.
  
 34. [FBC 1603]SHEET S1.01 CALLS FOR DETAIL 3/S2.01 FOR
 FOOTER AT STOREFRONT. THE DETAIL SAYS SEE PLAN FOR
 WIDTH OF STOREFRONT FOOTER. I DON?T SEE STOREFRONT
 FOOTER ON S1.01. IS THIS WF1 LIKE AT CMU INFILL WALL?
  
 SUBMITTALS AND PRODUCT APPROVALS:
 35. [FBC 107.3.4.1]A CONSTRUCTION GUARDRAIL DETAIL,
 PREPARED BY A DESIGN PROFESSIONAL LICENSED UNDER FS471
 OR FS481, IS REQUIRED TO BE SUBMITTED, REVIEWED AND
 ISSUED BY THE CITY OF WEST PALM BEACH. SUBJECT TO THE
 INSPECTOR?S DISCRETION, THIS MAY BE ACCEPTED IN THE
 FIELD AT TIME OF INSPECTION.
  
 36. [FBC AMENDED 107.2.1.2]PROVIDE PRODUCT APPROVALS
 FOR WINDOWS, WINDOW MULL(IF APPLICABLE), DOORS,
 TRANSOMS(IF APPLICABLE), LINTEL W/ SAFELOAD, SLIDING
 GLASS DOORS AND STOREFRONT, OR INDICATE THAT YOU WOULD
 LIKE THEM DEFFERED.
  
 37. [FBC AMENDED 107.2.1.2]PROVIDE SUBMITTAL FOR TRASH
 CHUTE, OR INDICATE THAT IT WILL BE DEFERRED.
  
 38. PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE
 PROPOSED? IF THE UNDERLAYMENT PRODUCT PROPOSED IS NOT
 ONE FOR WHICH WE HAVE TEST REPORTS ON FILE, THE
 FOLLOWING REPORTS ARE REQUIRED:
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  