| 2018-08-20 09:01:59 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18061140 |
| | REVIEWED: AUGUST 17, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. SEPARATE PERMIT REQUIRED FOR DEMO, |
| | ENGINEERING(CIVIL), LANDSCAPING, IRRIGATION, FENCING, |
| | DUMPSTER ENCLOSURE AND GENERATOR. |
| | |
| | 2. [FBC AMENDED 107.2.5]THE SUREVEY PROVIDED SHOWS |
| | EXISTING CONDITIONS, WHICH IS GOOD FOR THE DEMO PERMIT. |
| | PLEASE PROVIDE SURVEY TO SHOW NEW BUILDING ON THE SITE. |
| | SHOW LOWEST FOOR ELEVATION, AND PROVIDE ELEVATIONS IN |
| | NAVD88. |
| | |
| | 3. [FBC AMENDED 107.3.5]PLEASE UPDATE INDEX SHEET TO |
| | INCLUDE G-0.09. I WILL BE PUTTING APPROVAL STAMP ON |
| | THAT PAGE TO INDICATE ALL SHEETS REVIEWED. |
| | |
| | 4. SHEETS A-7.02 THRU A-7.09 NAME DESCRIPTION DOESN?T |
| | MATCH THE SHEET PROVIDED. EX: SHEET A7.02 SAYS WINDOW |
| | SCHEDULE ON INDEX SHEET, BUT IT IS ACTUALLY GLAZING |
| | DETAIL SHEET. |
| | |
| | 5. SHEET A-0.03 SHOW IN INDEX BUT NOT UPLOADED. PLEASE |
| | UPLOAD SHEET A-0.03 ACCESSIBILITY PLAN. |
| | |
| | 6. SHEET A-5.02 IS NOT UP-LOAD AND IT IS NEEDED FOR |
| | STAIR 2 DETAILS. |
| | |
| | 7. [FBC AMENDED 107.3.5]UPDATE INDEX SECTION FOR |
| | STRUCTURAL. IT SHOWS AS 8 STORY BUILDING AND SHEETS |
| | DON?T MATCH WHAT WAS UPLOADED. |
| | ALSO, SHEETS ARE MISSING. I CAN?T DO A FULL REVIEW |
| | UNTIL ALL STRUCTURAL SHEETS ARE PROVIDED. |
| | PLEASE REVIEW STRUCTURAL SECTION IN PROJECT DOX TO |
| | COMPARE TO ADJUSTED INDEX. |
| | |
| | 8. [FBC AMENDED 107.3.5]PLEASE UPDATE ALL DRAINGS |
| | INCLUDING LIFE SAFETY, FLOOR PLANS AND ROOF ACCESS TO |
| | SHOW HOW STAIRS WORK. LOOKING MAINLY AT AT THE FIRST |
| | FLOOR, 4 TH FLOOR(STAIR #2) ROOF LANDING(STAIR #1). |
| | SOME OF THE THINGS I SEE INCLUDE, BUT ARE NOT LIMITED |
| | TO: |
| | -STAIR 1 AT GROUND FLOOR SHOULD EXTEND INTO CORRIDOR |
| | SINCE THAT DISTANCE BETWEEN FLOORS IS GREATER THAN THE |
| | UPPER FLOORS. |
| | -STAIR 1 ROOF LANDING SHOULD HAVE GUARD RAIL AND NOT |
| | APPEAR TO CONTINUE GOING UP SINCE IT IS THE FINAL |
| | LANDING. IT ALSO EXITS ONTO ROOF DIFFERNTLY BETWEEN |
| | PLANS AND DETAILS. |
| | -STAIR 2 4 TH FLOOR LANDING SHOULD HAVE GUARD RAIL AND |
| | NOT APPEAR TO CONTINUE GOING UP SINCE IT IS THE FINAL |
| | LANDING. |
| | |
| | 9. PLEASE REVIEW ALL STAIRS AND SUPPLY MISSING SHEET |
| | A-5.02. |
| | ALSO, IF POSSIBLE ON SHEET A5.01 AND A5.02 CAN YOU KEEP |
| | THE SAME ORIENTAION AS THE PLANS FOR ENLARGED DETAILS. |
| | |
| | 10. UPDATE ALL LIFE SAFETY SHEETS FOR THE CURRENT CODE |
| | VERSION FBC 2017 6TH EDITION. I SEE THREE INSTANCES |
| | TOTAL(GENERAL NOTES, TRAVEL AND VERTICAL ORIENTED IN |
| | OCCUPANCY USE)ON ALL FOUR SHEETS. |
| | |
| | 11. SHEET A-S.03 STAIR SIGNAGE JPG. DIDN?T ATTACH TO |
| | DRAWING. ADD STAIR SIGNAGE DETAIL. |
| | |
| | 12. SHEET A-7.05 IMPACT INSULATION AND SOUND |
| | TRANSMISSION CLASS ARE FOR 6? SLAB. THE FLOORS IN THIS |
| | PROJECT ARE TO BE 8?. |
| | |
| | 13. SHEET A7.03 DOOR SCHEDULE REFERS TO ?SEE INTERIOR |
| | GLAZING?. I SEE REFERENCE TO TEMPERED GLASS, BUT WHAT |
| | ABOUT FIRE RATING ON DOORS IN THE CORRIDOR(2 HR RATED |
| | FIRE CORRIDOR).ALSO, THE NOTES BELOW INTERIOR GLAZING |
| | ARE FOR EXTERIOR DOORS. |
| | |
| | 14. [FBC ACCESSIBILITY 402.1]PROVIDE ACCESSIBLE ROUTE |
| | FROM PARKING LOT. |
| | |
| | 15. [FBC ACCESSIBILITY 208.2]PROVIDE DATA USED TO |
| | DETERMINE AMOUNT OF ADA SPOTS. |
| | |
| | 16. [FBC ACCESSIBILITY 404.2.3]DOOR ST2.1 APPEARS TO |
| | REDUCE THE WIDTH OF 199.1. VERIFY AND ADJUST IF |
| | APPLICABLE. |
| | |
| | 17. [FBC ACCESSIBILITY 606.2]CLEAR FLOOR SPACE. A CLEAR |
| | FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A |
| | FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING |
| | WITH 306 SHALL BE PROVIDED. |
| | |
| | 18. [FBC ACCESSIBILITY 606.3]HEIGHT. LAVATORIES AND |
| | SINKS SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER |
| | OF THE RIM OR COUNTER SURFACE 34 INCHES (865 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | THIS APPLIES TO THE 9 ADA UNITS. SHEETS A4.03(UNIT 0C), |
| | A4.06(UNIT 1C) AND A4.05(UNIT 1B). |
| | |
| | 19. [FBC ACCESSIBILITY 804.3]KITCHEN WORK SURFACE. IN |
| | RESIDENTIAL DWELLING UNITS REQUIRED TO COMPLY WITH 809, |
| | AT LEAST ONE 30 INCHES (760 MM) WIDE MINIMUM SECTION OF |
| | COUNTER SHALL PROVIDE A KITCHEN WORK SURFACE THAT |
| | COMPLIES WITH 804.3. |
| | |
| | 20. [FBC ACCESSIBILITY 804.3.2]HEIGHT. THE KITCHEN WORK |
| | SURFACE SHALL BE 34 INCHES (865 MM) MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND.THIS APPLIES TO THE 9 ADA UNITS. |
| | SHEETS A4.03(UNIT 0C), A4.06(UNIT 1C) AND A4.05(UNIT |
| | 1B). |
| | |
| | 21. [FBC AMENDED 107.3.5]IS DOOR 121.2 AT GARBAGE ROOM |
| | A ROLL-UP DOOR? HOW DOES THE TRASH ROOM FUNCTION? FROM |
| | SITE PLAN AND CIVIL PLANS IT LOOKS LIKE IT EXITS ONTO |
| | GRASS AND A CURB. |
| | |
| | 22. IF ELEVATOR PENTHOUSE GOES TO ELEVATION +50?-8? AS |
| | SHOWN ON A-5.04, ADJUST ELEVATIONS TO SHOW THE ELEVATOR |
| | PENTHOUSE AT THIS HEIGHT. |
| | |
| | 23. [FBC 720.2]SHEET A-6.01 GENERAL NOTES SHOWS |
| | INSULATION CODE REFERENCE FOR INSULATION AS FBC 719.2. |
| | IT IS NOW 720.2. |
| | |
| | 24. GROUND LEVEL CORRIDORS CALL FOR WALL TYPE 3. SHEET |
| | A-6.01 SHOW TYPE 3A TO BE 1 HOUR RATED. THIS CONFLICTS |
| | WITH LIFE SAFTEY PLAN WHERE IT IS ESTABLISHED AS A 2 |
| | HOUR RATED COORIDOR. PLEASE ADJUST WALL TYPE OR DETAIL |
| | AS NEEDED. PROVIDE UL |
| | |
| | 25. SHEET A-1.01 SHOWS THE TRASH ROOM AT 3 HOUR RATING |
| | AND SECTION A-5.05 SHOWS 2 HOUR WALL. THE WALL TYPE 9A |
| | SHOWN ON A-1.01 IS FOR 2 HOUR RATING. PLEASE |
| | CO-ORDINATE THE RATING TO MATCH(SAME COMMENT FOR |
| | STAIRS) |
| | |
| | 26. SHEET A-5.05, HOW IS TRASH CHUTE FIRE STOPPING |
| | INSTALLED IN THIS ASSEMBLY? WILL THAT BE PART OF |
| | DEFFERED SUBMITTAL? |
| | |
| | 27. SHEET A-5.05 SECTION 1 CALLS FOR 6 MIL AND 4? SLAB. |
| | STRUCTURAL, S1.01 FOUNDATION PLAN NOTES, IS CALLING FOR |
| | 5? SLAB WITH 10 MIL. PLEASE CO-ORDINATE WITH |
| | STRUCTURAL. |
| | |
| | 28. SHEET A3.01 CALL OUT TO A3.03 AT EXTERIOR WALLS. |
| | PLEASE PROVIDE THIS SHEET AS IT IS NOT PROVIDED AND |
| | ISN?T IN THE INDEX. ALSO, I THINK CALL OUT AT ELEVATER |
| | SHOULD BE 1/A-5.06 AND AT TRASH CHUTE IT SHOULD BE |
| | 1/5.05 |
| | |
| | 29. SHEET A3.02 CALL OUT TO A3.03 AT EXTERIOR WALLS. |
| | PLEASE PROVIDE THIS SHEET AS IT IS NOT PROVIDED AND |
| | ISN?T IN THE INDEX. |
| | |
| | 30. SHEET A-4.00 WHAT IS THE FINISH FOR ACCESSIBLE |
| | BALCONIES. [ANSI A137.1 ]IN FLOORING SUBMITTAL PROVIDE |
| | SPECIFICATION SHEET TO INCLUDE DYNAMIC COEFFICIENT OF |
| | FRICTION (DCOF) OF EXTERIOR FINISH BEING INSTALLED. |
| | |
| | 31. [FBC AMENDED 107.3.5.1]PROVIDE STRUCTURAL ANALYSIS |
| | FOR STRUCTURAL LOAD BEARING COMPONANTS INCLUDING |
| | DEFLECTIONS OF BEAMS AND SLABS. |
| | |
| | 32. [FBC 1603]SHEET S1.01 SHOWS (3)COLUMNS CC3 AT THE |
| | COVERE3D PARKING. WHEN I LOOK AT S1.02 I SEE 3 |
| | ADDITIONAL COLUMNS LABELED CC7 AND BEAM 2B-2. IT |
| | APPEARS THAT COLUMNS CC3 CARRIES THE BEAM AND |
| | ADDITIONAL OFFSET COLUMNS CC7. THE END OF 2B-2 ALSO |
| | BEARS ON SMALLER COLUMNS CC4. |
| | IS THIS THE CORRECT CONFIGURATION AND DOES CC7 FOUND ON |
| | FL 2-4 END AT BEAM IN 2 ND FLOOR FRAMING. |
| | |
| | 33. [FBC 1603]SAME COLUMNS CC3 APPEAR TO SUPPORT |
| | CANTILEVER APPROXIMATELY 9? FROM COLUMN TO BUILDINGS |
| | EDGE ABOVE FOR REMAINING OVERHANG OF PARKING AND THE |
| | REMAINING FLOORS. PLEASE CLARIFY THAT THIS IS CORRECT, |
| | OR ADJUST AS NEEDED TO TRANFER LOADS TO FOUNDATION. |
| | |
| | 34. [FBC 1603]SHEET S1.01 CALLS FOR DETAIL 3/S2.01 FOR |
| | FOOTER AT STOREFRONT. THE DETAIL SAYS SEE PLAN FOR |
| | WIDTH OF STOREFRONT FOOTER. I DON?T SEE STOREFRONT |
| | FOOTER ON S1.01. IS THIS WF1 LIKE AT CMU INFILL WALL? |
| | |
| | SUBMITTALS AND PRODUCT APPROVALS: |
| | 35. [FBC 107.3.4.1]A CONSTRUCTION GUARDRAIL DETAIL, |
| | PREPARED BY A DESIGN PROFESSIONAL LICENSED UNDER FS471 |
| | OR FS481, IS REQUIRED TO BE SUBMITTED, REVIEWED AND |
| | ISSUED BY THE CITY OF WEST PALM BEACH. SUBJECT TO THE |
| | INSPECTOR?S DISCRETION, THIS MAY BE ACCEPTED IN THE |
| | FIELD AT TIME OF INSPECTION. |
| | |
| | 36. [FBC AMENDED 107.2.1.2]PROVIDE PRODUCT APPROVALS |
| | FOR WINDOWS, WINDOW MULL(IF APPLICABLE), DOORS, |
| | TRANSOMS(IF APPLICABLE), LINTEL W/ SAFELOAD, SLIDING |
| | GLASS DOORS AND STOREFRONT, OR INDICATE THAT YOU WOULD |
| | LIKE THEM DEFFERED. |
| | |
| | 37. [FBC AMENDED 107.2.1.2]PROVIDE SUBMITTAL FOR TRASH |
| | CHUTE, OR INDICATE THAT IT WILL BE DEFERRED. |
| | |
| | 38. PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE |
| | PROPOSED? IF THE UNDERLAYMENT PRODUCT PROPOSED IS NOT |
| | ONE FOR WHICH WE HAVE TEST REPORTS ON FILE, THE |
| | FOLLOWING REPORTS ARE REQUIRED: |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | |