| 2018-07-26 11:50:51 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18061127 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. SOIL REPORT DIDN'T UPLOAD IN PROJECT DOX. PLEASE |
| | UPLOAD SOIL REPORT IN SUPPORTING DOCS FOLDER. |
| | |
| | 2. [FBC 107.3.5.3] PROVIDE SEDIMENT CONTROL PLAN TO |
| | KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT |
| | PROPERTIES AND STORM DRAINS. |
| | |
| | 3. OWNER OR OWNERS AGENT TO SIGN ENERGY CALCULATIONS. |
| | |
| | 4. [FBC R608.8]PROVIDE MINIMUM BEARING ON LINTEL |
| | SCHEDULE. PROVIDE LINTEL DOCUMENTATION FOR SAFE |
| | LOADING. |
| | |
| | 5. [FBC R806.3]IF BLOWN IN INSULATION IS BEING USED, |
| | HOW WILL YOU PREVENT IT FROM BLOCKING CROSS |
| | VENTILLATION? SHOW/EXPLAIN ON PLANS A-2.0 WHERE |
| | INSULATION IS CALLED OUT ON WALL SECTION |
| | INSULATION WIND BAFFLES, VENTING CHUTES, RAFTER VENTS |
| | OR INSULATION BAFFLES. KEEP THE BLOWN IN FROM GOING |
| | INTO THE EAVES. |
| | 6. [FBC R107.3.5.3]CONTINUE WALL SECTION ON A-2.0 |
| | THROUGH ROOF. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |