2018-06-30 09:22:1906/30/2018 1ST GA REVIEW**DENIED**
  
 1) PROVIDE SIGN BONA FIDA CONTRACT SHOWING TOTAL COST
 OF JOB. WPB AMEND TO THE FBC 109.3
  
 2) FLOOR PLAN LIST (4) 120 GALLON L.P TANK BUT
 ISOMETRIC PLAN SHOWS ONLY (3). PLEASE CLARIFY FBC
 107.2.1
  
 3) PIPING MATERIAL NOT LISTED ON ISOMETRIC. SHOW THE
 TYPE OF PIPE MATERIAL BEING INSTALLED, ALL PIPE SIZES,
 AND THE CORRESPONDING EHD NUMBER OF THE CORRUGATED
 STAINLESS STEEL TUBING
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 4) ISOMETRIC LIST SIZING CHARTS TO BE BASED OFF THE
 2017 6TH OF THE FBC WHICH IS THE CURRENT CODE IN AFFECT
 BUT CHARTS PROVIDED ARE 2014. SUBMIT TWO COPIES OF THE
 APPLICABLE SIZING TABLES USED TO SIZE THE GAS SYSTEM OR
 PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH
 SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD
 THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER
 TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND
 TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3.
  
 5) PLAN SHOWS INTERIOR GAS PIPING BY OTHERS. SHOW WHERE
 YOUR SCOPE OF WORK ENDS. YOUR WORK DESCRIPTION LIST
 PIPING UP TO 10' BUT THE 2ND STAGE REGULATOR IS SHOWING
 OVER 20'. PLEASE CLARIFY FBC 107.2.1
  