1 |
|
| Notes |
| Date |
Text |
| 2018-07-31 15:44:14 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: PROVISO TO BE CORRECTED UNDER MAIN | | | PERMIT #18040104 | | | | | | | | | 1. THE NEW 6" SANITARY FROM THE UPPER FLOORS CAN NOT | | | DISCHARGE TO THE SUMP PIT IN THE BASEMENT IT SHALL | | | CONNECT TO THE GRAVITY SYSTEM CONNECTED TO THE CITY | | | TAP. PER FBC PL 712.1 | | | | | | 2. THE CONDENSATE LINES FROM THE AC UNITS SHALL NOT | | | DISCHARGE TO THE SANITARY SYSTEM IT APPEARS TO BE | | | DISCHARGING INTO THE SUMP PIT. PER WEST PALM BEACH CITY | | | ORDINANCE SEC. 90-126.(5) | | | | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|