| Plan Review Notes For Permit 18061114 |
| Permit Number |
18061114 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-07-19 17:09:03 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | FBC B 1609 | | | | | | 1. THE PRODUCT APPROVAL DOES NOT HAVE PROVISION FOR | | | ENHANCED FASTENING | | | 2. THE ENHANCED FASTENING LETTER FROM THE ENGINEER DOES | | | NOT ADDRESS THE PANEL SEAM REQUIREMENT, WHICH AFFECTS | | | UPLIFT | | | 3. ENHANCED FASTENING ENGINEERING IS FOR ZONES 2 AND 3 | | | PRESSURES (-64, -94.6); -74.9 AND -125.9 ARE REQUIRED | | | 4. IF THE BUILDING OFFICIAL ELECTS TO ALLOW FOR YOU TO | | | UTILIZE ENHANCED FASTENING, HOW WILL YOU DESIGNATE THE | | | DIFFERENT ZONES FOR THE INSPECTOR? THIS METHOD OF | | | INSTALLATION IS TYPICALLY DONE ON FLAT DECKS BASE | | | SHEET; THE BASE SHEET CAN BE MARKED/CHALK LINED. HOW | | | WILL YOU ACCOMPLISH THIS ON THE METAL ROOF? | | | 5. ENGINEERING IS TO BE SIGNED, SEALED, DATED | | | ORIGINALS. WE SUGGEST THAT, IF YOU USE AN ENGINEER WHO | | | HAS A DIGITAL SEAL, YOU SUBMIT THE APPLICATION | | | DIGITALLY. FOR THIS ONE PERMIT, IF IT IS DETERMINED | | | THAT ENGINEERING IS ACCEPTABLE (BY B.O.), YOU MAY EMAIL | | | THE ORIGINAL TO ME AFTER THE BUILDING REVIEW IS PASSED. | | | |
|