| 2018-08-06 14:48:16 | 08/06/2018 1ST GAS REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SUBMIT TWO COPIES MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT |
| | (FIREPLACE) TO VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS |
| | RES. SEC. G2408.1. |
| | 2. SUBMIT TWO COPIES OF DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE THE |
| | ROOF AND ANCHORING DETAILS OF THE GAS VENT FOR |
| | FIREPLACE PER 2017 FBC FUEL GAS SECS. 502 THRU 505 OR |
| | 2017 FBC FUEL GAS RES. SECS. G2426 THRU G2429.1 |
| | 3. FIRE PLACE MANUFACTURES INSTALLATION INSTRUCTION |
| | SHALL BE ON SITE AT TIME OF INSTALLATION. |
| | 4. KEY NOTES 7 AND 8 ON PAGE P-1 AT FIRE PLACE DO NOT |
| | HAVE ANY VERBIAGE FOR PLAN KEY NOTES, PLEASE ADD NOTES |
| | OR DELETE NUMBER ON PLANS. WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 5. THERE APPEARS TO BE A CARPORT WHERE THE TANKLESS GAS |
| | WATER HEATER IS GOING TO BE LOCATED THIS REQUIRES |
| | SHOWING THE LOCATION OF THE TANKLESS WATER HEATER AND |
| | THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR |
| | WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION |
| | OF THE WATER HEATER SHALL COMPLY WITH THE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS. WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 6. PAGE P-1 HAS THE CARPORT LABEL AS A BEDROOM PLEASE |
| | CHANGE TO CARPORT, WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 7. SUBMIT TWO COPIES MANUFACTURER?S SPECIFICATIONS FOR |
| | THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION, WHERE APPLICABLE AND SHALL BE ON SITE, |
| | 2017 FBC FUEL GAS RES. SEC. G2421.1. |
| | 8. A ELECTRICAL OUT MAY BE REQUIRED FOR SOURCE OF |
| | IGNITION, WPB AMENDMENTS TO THE FBC SEC 105.1 |
| | 9. A SEPARATE GAS PERMIT SHALL BE REQUIRED, FBC WPB A |
| | 107.1 |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |