2018-07-10 10:18:591ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18061049
 7/10/2018
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE CART STORAGE GARAGE REQUIRES AN EXHAUST
 VENTILATION SYSTEM THAT IS IN COMPLIANCE WITH SECTION
 404 FBC M. IN ADDITION, PLEASE REFER TO SECTIONS 502.3-
 502.5.3 FBC M PERTAINING TO CART BATTERIES AND BATTERY
 CHARGING AND STORAGE AREA. MORE INFORMATION IS REQUIRED
 FOR A COMPLETE REVIEW INCLUDING THE NUMBER AND
 LOCATIONS OF CARTS BEING STORED, THE TYPE OF BATTERIES,
 AND THE BATTERY CHARGING AND STORAGE AREAS. PLEASE
 INCLUDE EXHAUST VENTLATION CALCULATIONS WITH THE
 REVISED PLANS AND DETAILS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  