Plan Review Notes
Plan Review Notes For Permit 18061049
Permit Number 18061049
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-06-26 15:05:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 0.01 - THERE ARE INDICATIONS THAT THIS IS A
 PROPOSED BUSINESS OCCUPANCY WITH ACCESSORY STORAGE.
  
 ON REVIEW OF THE FLORIDA LIFE SAFETY CODE IT WOULD
 APPEAR THAT THIS IS A PROPOSED STORAGE OCCUPANCY WITH
 ACCESSORY BUSINESS. THE SHOWROOM AREA IS MORE STORAGE
 THAT BUSINESS.
  
 PER NFPA 101
  
 3.3.190.3* BUSINESS OCCUPANCY. AN OCCUPANCY USED FOR
 THE
 TRANSACTION OF BUSINESS OTHER THAN MERCANTILE.
 (SAF-MER)
  
 A.3.3.190.3 BUSINESS OCCUPANCY. BUSINESS OCCUPANCIES
 INCLUDE
 THE FOLLOWING:
 (1) AIR TRAFFIC CONTROL TOWERS (ATCTS)
 (2) CITY HALLS
 (3) COLLEGE AND UNIVERSITY INSTRUCTIONAL BUILDINGS,
 CLASSROOMS
 UNDER 50 PERSONS, AND INSTRUCTIONAL LABORATORIES
 (4) COURTHOUSES
 (5) DENTISTS? OFFICES
 (6) DOCTORS? OFFICES
 (7) GENERAL OFFICES
 (8) OUTPATIENT CLINICS (AMBULATORY)
 (9) TOWN HALLS
  
 3.3.190.15* STORAGE OCCUPANCY. AN OCCUPANCY USED
 PRIMARILY
 FOR THE STORAGE OR SHELTERING OF GOODS, MERCHANDISE,
 PRODUCTS, OR
 VEHICLES. (SAF-IND)
  
 A.3.3.190.15 STORAGE OCCUPANCY. STORAGE OCCUPANCIES
 INCLUDE
 THE FOLLOWING:
 (1) BARNS
 (2) BULK OIL STORAGE
 (3) COLD STORAGE
 (4) FREIGHT TERMINALS
 (5) GRAIN ELEVATORS
 (6) HANGARS (FOR STORAGE ONLY)
 (7) PARKING STRUCTURES
 (8) TRUCK AND MARINE TERMINALS
 (9) WAREHOUSES
 STORAGE OCCUPANCIES ARE CHARACTERIZED BY THE PRESENCE
 OF
 RELATIVELY SMALL NUMBERS OF PERSONS IN PROPORTION TO
 THE AREA.
  
 HOWEVER, THIS ALSO APPEARS TO BE A MIXED NON-SEPARATED
 OCCUPANCY, WHICH WOULD REQUIRE THE MOST STRINGENT CODE
 REQUIRMENTS OF THE TWO.
  
 38.1.3 MULTIPLE OCCUPANCIES.
 38.1.3.1 GENERAL.
 38.1.3.1.1 ALL MULTIPLE OCCUPANCIES SHALL BE IN
 ACCORDANCE WITH
 6.1.14 AND 38.1.3.
 38.1.3.1.2 WHERE THERE ARE DIFFERENCES IN THE SPECIFIC
 REQUIREMENTS
 IN THIS CHAPTER AND PROVISIONS FOR MIXED OCCUPANCIES OR
 SEPARATED
 OCCUPANCIES AS SPECIFIED IN 6.1.14.3 AND 6.1.14.4, THE
 REQUIREMENTS
 OF THIS CHAPTER SHALL APPLY.
  
 PLEASE REVIEW, CORRECT OR CLARIFY WITH SPECIFIC LIFE
 SAFETY CODE REFERENCES.
  
  
  
 2) SHEET A 2.01 - THOUGH THE CODE MAY ALLOW FOR
 NON-SEPARATED OCCUPANCY, THE HAZARD OF THE STORAGE AREA
 SHALL BE CONSIDERED.
  
 WHAT IS THE COMPLETE EXTENT OF THE STORAGE AREA?
  
 WHAT WORK WILL OCCUR IN THESE SPACES?
  
 WHERE WILL BATTERIES BE STORED?
  
 WILL THERE BE ACID STORED?
  
 WILL THERE BE OIL OR GAS STORED?
  
 PLEASE PROVIDE AS MUCH DETAILED INFORMATION AS
 POSSIBLE.
  
 PER NFPA 101, CHAPTER 6, CLASSIFICATION OF OCCUPANCY
  
  
 6.2 HAZARD OF CONTENTS.
 6.2.1 GENERAL.
 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF
 CONTENTS SHALL
 BE THE RELATIVE DANGER OF THE START AND SPREAD OF FIRE,
 THE DANGER OF
 SMOKE OR GASES GENERATED, AND THE DANGER OF EXPLOSION
 OR OTHER
 OCCURRENCE POTENTIALLY ENDANGERING THE LIVES AND SAFETY
 OF THE
 OCCUPANTS OF THE BUILDING OR STRUCTURE.
 6.2.1.2 HAZARD OF CONTENTS SHALL BE CLASSIFIED BY THE
 REGISTERED
 DESIGN PROFESSIONAL (RDP) OR OWNER AND SUBMITTED TO THE
 AUTHORITY HAVING JURISDICTION FOR REVIEW AND APPROVAL
 ON THE BASIS
 OF THE CHARACTER OF THE CONTENTS AND THE PROCESSES OR
 OPERATIONS
 CONDUCTED IN THE BUILDING OR STRUCTURE.
 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT
 DEGREES OF
 HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS OF A
 BUILDING OR STRUCTURE,
 THE MOST HAZARDOUS SHALL GOVERN THE CLASSIFICATION,
 UNLESS
 HAZARDOUS AREAS ARE SEPARATED OR PROTECTED AS SPECIFIED
 IN SECTION
 8.7 AND THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH
 43.
  
  
 8.7 SPECIAL HAZARD PROTECTION.
 8.7.1 GENERAL.
 8.7.1.1* PROTECTION FROM ANY AREA HAVING A DEGREE OF
 HAZARD
 GREATER THAN THAT NORMAL TO THE GENERAL OCCUPANCY OF
 THE
 BUILDING OR STRUCTURE SHALL BE PROVIDED BY ONE OF THE
 FOLLOWING
 MEANS:
 (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT
 WINDOWS THAT
 HAS A 1-HOUR FIRE RESISTANCE RATING IN ACCORDANCE WITH
 SECTION 8.3
 (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING
 SYSTEMS IN
 ACCORDANCE WITH SECTION 9.7
 (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD
 IS SEVERE
 OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11 THROUGH 43
  
 A RATED SEPARATION OF HAZARD, NOT JUST OCCUPANCY, MAY
 BE REQUIRED BASED ON THE WHAT IS BEING DONE IN THE
 STORAGE AREAS.
  
 PLEASE REVIEW, CORRECT WITH REQUIRED SEPARATION, OR
 JUSTIFY WITH DETAILS WHY NOT.
  
  
  
  
 3) SHEET A 0.01 - UNDER THE BUILDING AND CONSTRUCTION
 DATA SECTION THERE IS AN INDICATION OF
 "NON-SPRINKLERED"
  
 UNDER THE INTERIOR FINISHES SECTION THERE IS AN
 INDICATION FO "SPRINKLERED"
  
 PLEASE REVIEW AND CORRECT WHICH ONE IS ACCURATE.
  
  
  
  
 4) SHEET A 2.01 THERE IS A NORTH EAST EXIT DOOR
 INDICATING OUTSWING BUT ON SHEET S 1.0 & E 1 THIS SAME
 DOOR IS INDICATED AS INSWING.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 5) SHEET A 2.01 THERE IS AN INDICATION OF EXIT TRAVEL
 PATH THROUGH THE EAST DOUBLE DOORS BUT ON SHEET E 2
 THERE IS NO EXIT SIGNAGE OVER THIS DOOR.
  
 PLEASE REVIEW, CORRECT OR JUSTIFY.
  
  
  
  
 6) SHEET A 2.01 AND E 2 - IN THE CENTER BUSINESS AREA
 THERE IS A CORRIDOR. AT THE EAST END OF THE CORRIDAR BY
 THE BREAK AREA THERE IS NO EXIT SIGN. PEOPLE IN THIS
 CORRIDOR NEED TO BE DIRECTED TO NEAREST EXIT.
  
 PLEASE PALCE AN EXIT SIGN AND THE END OF THE CORRIDOR
 BY THE BREAK AREA.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
  
  