| 2018-06-26 15:05:28 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET A 0.01 - THERE ARE INDICATIONS THAT THIS IS A |
| | PROPOSED BUSINESS OCCUPANCY WITH ACCESSORY STORAGE. |
| | |
| | ON REVIEW OF THE FLORIDA LIFE SAFETY CODE IT WOULD |
| | APPEAR THAT THIS IS A PROPOSED STORAGE OCCUPANCY WITH |
| | ACCESSORY BUSINESS. THE SHOWROOM AREA IS MORE STORAGE |
| | THAT BUSINESS. |
| | |
| | PER NFPA 101 |
| | |
| | 3.3.190.3* BUSINESS OCCUPANCY. AN OCCUPANCY USED FOR |
| | THE |
| | TRANSACTION OF BUSINESS OTHER THAN MERCANTILE. |
| | (SAF-MER) |
| | |
| | A.3.3.190.3 BUSINESS OCCUPANCY. BUSINESS OCCUPANCIES |
| | INCLUDE |
| | THE FOLLOWING: |
| | (1) AIR TRAFFIC CONTROL TOWERS (ATCTS) |
| | (2) CITY HALLS |
| | (3) COLLEGE AND UNIVERSITY INSTRUCTIONAL BUILDINGS, |
| | CLASSROOMS |
| | UNDER 50 PERSONS, AND INSTRUCTIONAL LABORATORIES |
| | (4) COURTHOUSES |
| | (5) DENTISTS? OFFICES |
| | (6) DOCTORS? OFFICES |
| | (7) GENERAL OFFICES |
| | (8) OUTPATIENT CLINICS (AMBULATORY) |
| | (9) TOWN HALLS |
| | |
| | 3.3.190.15* STORAGE OCCUPANCY. AN OCCUPANCY USED |
| | PRIMARILY |
| | FOR THE STORAGE OR SHELTERING OF GOODS, MERCHANDISE, |
| | PRODUCTS, OR |
| | VEHICLES. (SAF-IND) |
| | |
| | A.3.3.190.15 STORAGE OCCUPANCY. STORAGE OCCUPANCIES |
| | INCLUDE |
| | THE FOLLOWING: |
| | (1) BARNS |
| | (2) BULK OIL STORAGE |
| | (3) COLD STORAGE |
| | (4) FREIGHT TERMINALS |
| | (5) GRAIN ELEVATORS |
| | (6) HANGARS (FOR STORAGE ONLY) |
| | (7) PARKING STRUCTURES |
| | (8) TRUCK AND MARINE TERMINALS |
| | (9) WAREHOUSES |
| | STORAGE OCCUPANCIES ARE CHARACTERIZED BY THE PRESENCE |
| | OF |
| | RELATIVELY SMALL NUMBERS OF PERSONS IN PROPORTION TO |
| | THE AREA. |
| | |
| | HOWEVER, THIS ALSO APPEARS TO BE A MIXED NON-SEPARATED |
| | OCCUPANCY, WHICH WOULD REQUIRE THE MOST STRINGENT CODE |
| | REQUIRMENTS OF THE TWO. |
| | |
| | 38.1.3 MULTIPLE OCCUPANCIES. |
| | 38.1.3.1 GENERAL. |
| | 38.1.3.1.1 ALL MULTIPLE OCCUPANCIES SHALL BE IN |
| | ACCORDANCE WITH |
| | 6.1.14 AND 38.1.3. |
| | 38.1.3.1.2 WHERE THERE ARE DIFFERENCES IN THE SPECIFIC |
| | REQUIREMENTS |
| | IN THIS CHAPTER AND PROVISIONS FOR MIXED OCCUPANCIES OR |
| | SEPARATED |
| | OCCUPANCIES AS SPECIFIED IN 6.1.14.3 AND 6.1.14.4, THE |
| | REQUIREMENTS |
| | OF THIS CHAPTER SHALL APPLY. |
| | |
| | PLEASE REVIEW, CORRECT OR CLARIFY WITH SPECIFIC LIFE |
| | SAFETY CODE REFERENCES. |
| | |
| | |
| | |
| | 2) SHEET A 2.01 - THOUGH THE CODE MAY ALLOW FOR |
| | NON-SEPARATED OCCUPANCY, THE HAZARD OF THE STORAGE AREA |
| | SHALL BE CONSIDERED. |
| | |
| | WHAT IS THE COMPLETE EXTENT OF THE STORAGE AREA? |
| | |
| | WHAT WORK WILL OCCUR IN THESE SPACES? |
| | |
| | WHERE WILL BATTERIES BE STORED? |
| | |
| | WILL THERE BE ACID STORED? |
| | |
| | WILL THERE BE OIL OR GAS STORED? |
| | |
| | PLEASE PROVIDE AS MUCH DETAILED INFORMATION AS |
| | POSSIBLE. |
| | |
| | PER NFPA 101, CHAPTER 6, CLASSIFICATION OF OCCUPANCY |
| | |
| | |
| | 6.2 HAZARD OF CONTENTS. |
| | 6.2.1 GENERAL. |
| | 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF |
| | CONTENTS SHALL |
| | BE THE RELATIVE DANGER OF THE START AND SPREAD OF FIRE, |
| | THE DANGER OF |
| | SMOKE OR GASES GENERATED, AND THE DANGER OF EXPLOSION |
| | OR OTHER |
| | OCCURRENCE POTENTIALLY ENDANGERING THE LIVES AND SAFETY |
| | OF THE |
| | OCCUPANTS OF THE BUILDING OR STRUCTURE. |
| | 6.2.1.2 HAZARD OF CONTENTS SHALL BE CLASSIFIED BY THE |
| | REGISTERED |
| | DESIGN PROFESSIONAL (RDP) OR OWNER AND SUBMITTED TO THE |
| | AUTHORITY HAVING JURISDICTION FOR REVIEW AND APPROVAL |
| | ON THE BASIS |
| | OF THE CHARACTER OF THE CONTENTS AND THE PROCESSES OR |
| | OPERATIONS |
| | CONDUCTED IN THE BUILDING OR STRUCTURE. |
| | 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT |
| | DEGREES OF |
| | HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS OF A |
| | BUILDING OR STRUCTURE, |
| | THE MOST HAZARDOUS SHALL GOVERN THE CLASSIFICATION, |
| | UNLESS |
| | HAZARDOUS AREAS ARE SEPARATED OR PROTECTED AS SPECIFIED |
| | IN SECTION |
| | 8.7 AND THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH |
| | 43. |
| | |
| | |
| | 8.7 SPECIAL HAZARD PROTECTION. |
| | 8.7.1 GENERAL. |
| | 8.7.1.1* PROTECTION FROM ANY AREA HAVING A DEGREE OF |
| | HAZARD |
| | GREATER THAN THAT NORMAL TO THE GENERAL OCCUPANCY OF |
| | THE |
| | BUILDING OR STRUCTURE SHALL BE PROVIDED BY ONE OF THE |
| | FOLLOWING |
| | MEANS: |
| | (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT |
| | WINDOWS THAT |
| | HAS A 1-HOUR FIRE RESISTANCE RATING IN ACCORDANCE WITH |
| | SECTION 8.3 |
| | (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING |
| | SYSTEMS IN |
| | ACCORDANCE WITH SECTION 9.7 |
| | (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD |
| | IS SEVERE |
| | OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11 THROUGH 43 |
| | |
| | A RATED SEPARATION OF HAZARD, NOT JUST OCCUPANCY, MAY |
| | BE REQUIRED BASED ON THE WHAT IS BEING DONE IN THE |
| | STORAGE AREAS. |
| | |
| | PLEASE REVIEW, CORRECT WITH REQUIRED SEPARATION, OR |
| | JUSTIFY WITH DETAILS WHY NOT. |
| | |
| | |
| | |
| | |
| | 3) SHEET A 0.01 - UNDER THE BUILDING AND CONSTRUCTION |
| | DATA SECTION THERE IS AN INDICATION OF |
| | "NON-SPRINKLERED" |
| | |
| | UNDER THE INTERIOR FINISHES SECTION THERE IS AN |
| | INDICATION FO "SPRINKLERED" |
| | |
| | PLEASE REVIEW AND CORRECT WHICH ONE IS ACCURATE. |
| | |
| | |
| | |
| | |
| | 4) SHEET A 2.01 THERE IS A NORTH EAST EXIT DOOR |
| | INDICATING OUTSWING BUT ON SHEET S 1.0 & E 1 THIS SAME |
| | DOOR IS INDICATED AS INSWING. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 5) SHEET A 2.01 THERE IS AN INDICATION OF EXIT TRAVEL |
| | PATH THROUGH THE EAST DOUBLE DOORS BUT ON SHEET E 2 |
| | THERE IS NO EXIT SIGNAGE OVER THIS DOOR. |
| | |
| | PLEASE REVIEW, CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | |
| | 6) SHEET A 2.01 AND E 2 - IN THE CENTER BUSINESS AREA |
| | THERE IS A CORRIDOR. AT THE EAST END OF THE CORRIDAR BY |
| | THE BREAK AREA THERE IS NO EXIT SIGN. PEOPLE IN THIS |
| | CORRIDOR NEED TO BE DIRECTED TO NEAREST EXIT. |
| | |
| | PLEASE PALCE AN EXIT SIGN AND THE END OF THE CORRIDOR |
| | BY THE BREAK AREA. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |