| 2018-08-12 11:01:55 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. FBC B 406, THE 6000 SF AREA CART STORAGE AREA |
| | APPEARS TO BE AN "ENCLOSED PARKING GARAGE". FBC B |
| | 406.5.10, MECHANICAL PAGES SHOW "EXISTING" VENTS BUT DO |
| | NOT SHOW A VENTILATION SYSTEM FOR THE GARAGE AREA. OUR |
| | RECORDS SHOW THE MOST RECENT PERMIT, 12030654, |
| | DESIGNATES THE GOLF CART STORAGE AREA SHOWN ON THE |
| | PROPOSED PLAN AS "PRODUCT STORAGE" FOR A CONSTRUCTION |
| | PRODUCT COMPANY, AND SOME OF THE OFFICES ARE NOT SHOWN. |
| | |
| | IT APPEARS THAT THIS IS A CHANGE OF OCCUPANCY OR USE. |
| | REVISE PLAN TO SHOW COMPLIANCE. |
| | |
| | 2. PLEASE SUBMIT A RECORDS RESEARCH REQUEST. IT APPEARS |
| | THAT SOME ITEMS SHOWN AS "EXISTING" WERE INSTALLED |
| | WITHOUT A PERMIT, OR INSTALLED WITH A PERMIT BUT PERMIT |
| | WAS NOT INSPECTED AND CLOSED. PLEASE INCORPORATE |
| | EXPIRED PERMITS INTO THE SCOPE OF THIS PERMIT. NOTE |
| | THAT 05120912 MECHANICAL PERMIT FAILED FOR LACK OF A |
| | SHUT DOWN TEST AND OTHER ITEMS AND WAS NOT RESCHEDULED; |
| | SUBSEQUENT 16070647 HAS NO INSPECTIONS, BUT THE PLAN |
| | SHOWS MECHANICAL EQUIPMENT AS "EXISTING". |
| | |
| | THE LAST PERMIT FOR THIS SPACE, 12030654, DOES NOT |
| | MATCH THE FLOOR PLAN SHOWN AS "EXISTING". PLAN SHOULD |
| | BE REVISED TO SHOW THE SPACES WHICH APPEAR TO HAVE BEEN |
| | INSTALLED WITHOUT A PERMIT AS "PROPOSED" OR NOTED THAT |
| | IT WAS PREVIOUSLY INSTALLED WITHOUT A PERMIT AND IS |
| | BEING LEGALIZED WITH THE CURRENT PROPOSED PERMIT. |
| | |
| | 3. FBC EB 301.1, APPLICANT IS TO ELECT A METHOD OF |
| | COMPLIANCE. REVISE PLAN TO INCLUDE FBC 2017 EXISTING |
| | BUILDING CODE AND METHOD ELECTED FOR THE ALTERATION. |
| | INDICATE THAT THIS IS A CHANGE OF OCCUPANCY OR USE AS |
| | APPLICABLE. MOST COMMON METHOD IS FBC EB ALTERATION |
| | LEVEL II AND FBC EB CHAPTER 10, CHANGE OF OCCUPANCY. |
| | |
| | 4. FBC 107, PROVIDE A DEMO PLAN. A0.01 STATES THAT |
| | INTERIOR DEMO WAS DONE UNDER A SEPARATE PERMIT. IT |
| | APPEARS THAT BATHROOMS AND OTHER ITEMS WERE DEMOLISHED; |
| | EITHER PROVIDE A PERMIT NUMBER FOR THIS WORK OR |
| | INCORPORATE THE DEMO WORK DONE WITHOUT PERMIT INTO THIS |
| | PERMIT. |
| | |
| | 5. AS I DO NOT HAVE ALL RECORDS READILY AVAILABLE TO |
| | ME, IT IS NOT CLEAR IF THE OVERHEAD DOORS AND RELATED |
| | OPENINGS WERE PERMITTED. IF BUILDING ENVELOPE WAS |
| | AFFECTED BY WORK WITHOUT PERMIT, INCLUDE WIND DESIGN |
| | CRITERIA, PRODUCT APPROVALS. |
| | |
| | 6. SOME OF THE ABOVE REQUESTS THAT CERTAIN ITEMS BE |
| | INCORPORATED INTO THIS PERMIT. IF ARCHITECT, ENGINEER, |
| | AND/OR CONTRACTOR DO NOT WISH TO TAKE RESPONSIBILITY |
| | FOR THESE ITEMS, THE WORK INSTALLED WITHOUT A PERMIT |
| | CAN BE LEGALIZED VIA A SEPARATE PERMIT, BUT THOSE |
| | ISSUES ARE TO BE RESOLVED PRIOR TO ISSUANCE OF THIS NEW |
| | PERMIT WHICH CALLS THE WORK INSTALLED WITHOUT PERMIT |
| | "EXISTING". |
| | |