2018-12-12 14:38:07PASS PROVISO
 1) PROVIDE DUCT SIZE FOR 1ST FLOOR STORAGE ROOM 136
 SECTION 107 FBC 2017 FOR 1ST INSPECTION.
 2) PROVIDE RETURN AIR DUCT IN HER OFFICE ROOM 114 1ST
 FLOOR
 SECTION M1602.3 BALANCED RETURN AIR 2017 RESIDENTIAL
 CODE.
 3) REFER TO SECTION M1305 APPLIANCE ACCESS FOR
 INSPECTION
 SERVICE, REPAIR AND REPLACEMENT 2017 RESIDENTIAL CODE.
 4) REFER TO SECTION 403.3.6 AIR HANDLING UNITS 2017
 FLORIDA ENERGY CODE.
 HAVE ALL 4 COMMENTS COMPLETED FOR 1ST INSPECTION.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676