Plan Review Notes
Plan Review Notes For Permit 18061038
Permit Number 18061038
Review Stop G
Sequence Number 1
Notes
Date Text
2018-07-26 17:23:381ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 SOME COMMENT MAY NOT APPLY BUT ARE PROVIDED FOR
 REFERENCES.
  
 1. ISOMETRIC DRAWING NEED TO CLEARLY SHOW THE LENGTH OF
 ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
 2. GAS METER SHOWN DOWNSTREAM OF REGULATOR SHUTOFF
 VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH MP
 REGULATOR. 2017 FBC FUEL GAS RES. SEC. G2420.4.
 3. PLEASE LABEL THE TYPE OF GAS (LP OR NATURAL) ON
 ISOMETRIC P0.4. WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 4. SHOW ALL SHUT-OFF VALVE TO EACH APPLIANCE IN
 ISOMETRIC, 2017 FBC FUEL GAS SEC. 409.4, FBC FUEL GAS
 RES. SEC. G2420.4
 5. THE PLANS ON P1.1 SHOWS A GAS DRYER DOWNSTAIRS BUT
 ON THE P1.2 SECOND FLOOR SHOWS THE SECOND DRYER BUT NOT
 LABELED AS GAS OR NO GAS SHOWN TO IT. IS IT GAS AND IF
 IT IS PLEASE LABEL ON PLANS, WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 6. SUBMIT COMBUSTION AIR CALCULATIONS FOR GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FBC R
 G2407.9.3. COMBINED COMBUSTION AIR AND VENTILATION AIR
 SYSTEM.
 7. PLEASE SUBMIT A DETAIL SHOWING THE TYPE, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL
 GAS RES. SECS. G2426 THRU G2429.1
 8. PLEASE SHOW ALL SHUTOFF VALVES ON GAS ISOMERIC, 2017
 FBC FUEL GAS RES. SEC. 404.15, 411.
 9. WATER HEATERS WILL REQUIRE A SEPARATE IGNITION
 SOURCE AND IT IS BEING LABELED ON A SEPARATE CIRCUIT
 FOR IGNITION ON TANKLESS, WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 10. PLEASE PROVIDE ON ALL APPLIANCES MANUFACTURES
 SPECIFICATION, FBC FG R2434.1 GENERAL.
 11. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS RES. SEC. G2421.1.
 12. PLEASE SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC
 FUEL GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2,
 & G2413.3.
 13. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION 2017 FBC FUEL GAS SEC. 402.2 AND 301.3 OR
 2017 FBC FUEL GAS RES. SEC. G2413.2 AND G2404.3.
 14. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER
 A ROOF. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE
 GRILL TO VERIFY IF THE HOOD IS NEEDED. FGC SEC.305.1,
 FBC-RES. SEC.G2408.1.
 15. SHOW THE LOCATION OF THE TANKLESS WATER HEATER AND
 THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN CAN BE HAND DRAWN. WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
 16. SUBMIT SPECIFICATION FOR THE GENERATOR. THE
 MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR SHALL
 BE ONSITE FOR FINAL GAS INSPECTION. THE GENERATOR SHALL
 BE LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE
 GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  