2018-07-08 16:42:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E0.1, LIGHTING ENERGY CONSERVATION NOTE
 SPECIFIES THE WRONG CODE FOR DESIGN. PROVIDE
 CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES ABOVE)
 2. SHEET E0.1, CONSTRUCTION ELECTRICAL NOTES, NOTE 1FOR
 AFCI PROTECTION SPECIFIES THE WONG CODE FOR DESIGN AND
 DOES NOT INCLUDE ALL AREAS REQUIRED TO HAVE AFCI
 PROTECTION. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. SOME
 AREAS WILL REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES
 ABOVE); NEC 210.12
 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 4. SHEEY E3.1, REMOVE ITEMS NOT ASSOCIATED WITH THIS
 PLAN SUCH AS GENERATOR LOAD SHED CALCULATIONS AND
 GENERATOR NOTES. FYI, WHY IS THERE A 40% REDUCTION OF
 THE LOADS BEING SHED FROM GENERATOR? THEY WOULD EITHER
 BE SHED COMPLETELY OR NOT, THERE IS NO DEMAND FACTOR
 FOR THIS. WPB FBC 107.2.1
 5. RECEPTACLES IS STORAGE AREAS REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8
 6. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC
 210.8(D)
 7. PANEL SCHEDULES DO NOT INDICATE THE REQUIRED AFCI
 PROTECTION PER NOTES FOR EACH PANEL. SOME CIRCUITS
 REQUIRE AFCI AND GFCI PROTECTION. PROVIDE CORRECTION.
 NEC 210.8, 210.12, 408.4; WPB FBC 107.2.1
 8. PANEL SCHEDULE FOR PANEL P IS INCOMPLETE. HOW IS THE
 LOAD FOR THIS PANEL DETERMINED WITH NO DESCRIPTION.
 PROVIDE CORRECTION. WPB FBC 107.2.1; NEC 220, 408.4
 9. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 10. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 11. PROVIDE AIC RATING OF TRANSFER SWITCH AND PANELS.
 NEC 110.3, 110.9
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  