Plan Review Notes
Plan Review Notes For Permit 18061031
Permit Number 18061031
Review Stop P
Sequence Number 1
Notes
Date Text
2018-08-14 18:18:5908/14/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ISOMETRIC DRAWING ON A-5 AND LAYOUT REQUIRE BRANCHES
 AND STACKS THAT SHALL BE SIZED IN ACCORDANCE WITH TABLE
 P3005.4.1. DIVIDE INTO BATHROOM GROUPS AND VENT EACH
 GROUP AND RUN STACK OF WASHING MACHINE DOWNSTREAM FROM
 FIRST BATHROOM GROUP, REFER TO 2017 FBC R3005.4.
 2. CLEAN OUT ARE NOT REQUIRED AT END OF RUN PER CODE.
 3. A THREE INCH (3") DRAIN LINE RECOMMENDED AT WASHING
 MACHINE AS MOST MANUFACTURES REQUIRE BECAUSE OF THE
 WATER DISCHARGE VOLUME IN NEW MODELS.
 4. TRUNK LINE MAYBE BEST RAN AWAY FROM SHOWER RECESS
 BECAUSE OF DEPTH TO FINAL INVERT ELEVATION OUT OF
 FOUNDATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  