| Plan Review Notes For Permit 18061031 |
| Permit Number |
18061031 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-08-14 18:18:59 | 08/14/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. ISOMETRIC DRAWING ON A-5 AND LAYOUT REQUIRE BRANCHES | | | AND STACKS THAT SHALL BE SIZED IN ACCORDANCE WITH TABLE | | | P3005.4.1. DIVIDE INTO BATHROOM GROUPS AND VENT EACH | | | GROUP AND RUN STACK OF WASHING MACHINE DOWNSTREAM FROM | | | FIRST BATHROOM GROUP, REFER TO 2017 FBC R3005.4. | | | 2. CLEAN OUT ARE NOT REQUIRED AT END OF RUN PER CODE. | | | 3. A THREE INCH (3") DRAIN LINE RECOMMENDED AT WASHING | | | MACHINE AS MOST MANUFACTURES REQUIRE BECAUSE OF THE | | | WATER DISCHARGE VOLUME IN NEW MODELS. | | | 4. TRUNK LINE MAYBE BEST RAN AWAY FROM SHOWER RECESS | | | BECAUSE OF DEPTH TO FINAL INVERT ELEVATION OUT OF | | | FOUNDATION. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|