Plan Review Notes
Plan Review Notes For Permit 18061031
Permit Number 18061031
Review Stop E
Sequence Number 1
Notes
Date Text
2018-07-26 10:59:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE 17 FOR AFCI COMPLIANCE IS NOT TO CODE. PER
 CODE, ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
 2. NOTE 21 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 3. PROVIDE LOCATION OF INTERIOR PANEL. WPB FBC 107.2.1
 4. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. ONE SMOKE ALARM IS SHOWN LESS THAN 6
 FEET FROM A COOKING APPLIANCE. FOR THIS ALARM, PROVIDE
 CORRECTION OF LOCATION AND SPECIFY TYPE PER FBC RE
 R314.3.1. FBC RE R314.3, R315.1; WPB FBC 107.2.1
 5. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE (BOTH
 UNITS), INCLUDE EXISTING AND NEW LOADS TO CONFIRM
 CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220,
 408.30; FBC RE E3602.2
 6. RISER DIAGRAM SHOWS THE ELECTRICAL RISER CONTAINING
 THREE 3/0 CONDUCTORS, WHICH IS RATED FOR 200 AMPS.
 BASED ON THE LOAD CALCULATION OF ONE UNIT BEING 164
 AMPS, IT APPEARS THIS WIRE IS NOT SUFFICIENT TO HANDLE
 THE LOAD. PROVIDE CORRECTION. NEC 215.2, 310.15(B)(16);
 FBC RE E3602.1
 7. RISER DIAGRAM SHOWS THE SERVICE AS EXISTING ON A
 STRUCTURE THAT IS NOT BUILT YET, SO OBVIOUSLY THIS IS
 NOT EXISTING AND WILL BE TREATED AS A NEW SERVICE.
 REMOVE IDENTIFICATION AS EXISTING. WPB FBC 107.2.1
 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3
 9. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9; FBC RE E3603.3
 10. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 11. LIGHT IN CLOSET IS NOT SPECIFIED. EITHER SPECIFY
 TYPE OF FIXTURE, OR THAT ALL LIGHTING IN CLOSETS WILL
 COMPLY WITH THE FOLLOWING CODE: NEC 410.16; FBC RE
 E4003.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  