| Plan Review Notes For Permit 18061007 |
| Permit Number |
18061007 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-08-07 08:38:01 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE SHOW WINDOW OUTLETS PER 210.62 | | | 2. PLAN DOES NOT SHOW LOCATION OF MECHANICAL EQUIPMENT. | | | PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C | | | EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC | | | 210.63 | | | 3. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS | | | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT | | | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 | | | 4. PROVIDE AUTOMATIC CONTROL FOR SIGN CIRCUIT. FBC EC | | | 405.2.4 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | | SHEETS?. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|